| 2016-06-17 16:42:19 | 2ND REVIEW: FBC 2014 5TH ED. RESIDENTIAL |
| | |
| | DENIED COMMENTS FROM FIRST REVIEW WERE NOT ADDRESSED AS |
| | FOLLOWS: |
| | |
| | PLEASE DEMONSTRATE THE EXISTENCE OF PROVIDE DETAIL TO |
| | ASSURE THE INSTALLATION OF AN EQUIPOTENTIAL BONDING |
| | GRID AT THE PERIMETER SURFACES THAT EXTEND LESS THAN 3 |
| | FEET (914 MM) BEYOND THE INSIDE WALL OF THE POOL |
| | |
| | SECTION E4204 BONDING |
| | |
| | E4204.1 PERFORMANCE. |
| | THE EQUIPOTENTIAL BONDING REQUIRED BY THIS SECTION |
| | SHALL BE INSTALLED TO REDUCE VOLTAGE GRADIENTS IN THE |
| | POOL AREA AS PRESCRIBED. |
| | |
| | 2. PERIMETER SURFACES. THE PERIMETER SURFACE SHALL |
| | EXTEND FOR 3 FEET (914 MM) HORIZONTALLY BEYOND THE |
| | INSIDE WALLS OF THE POOL AND SHALL INCLUDE UNPAVED |
| | SURFACES, POURED CONCRETE SURFACES AND OTHER TYPES OF |
| | PAVING. PERIMETER SURFACES THAT EXTEND LESS THAN 3 FEET |
| | (914 MM) BEYOND THE INSIDE WALL OF THE POOL AND THAT |
| | ARE SEPARATED FROM THE POOL BY A PERMANENT WALL OR |
| | BUILDING 5 FEET (1524 MM) OR MORE IN HEIGHT SHALL |
| | REQUIRE EQUIPOTENTIAL BONDING ON THE POOL SIDE OF THE |
| | PERMANENT WALL OR BUILDING. BONDING TO PERIMETER |
| | SURFACES SHALL BE PROVIDED AS SPECIFIED IN ITEM 2.1 OR |
| | 2.2 AND SHALL BE ATTACHED TO THE POOL, SPA, OR HOT TUB |
| | REINFORCING STEEL OR COPPER CONDUCTOR GRID AT A MINIMUM |
| | OF FOUR POINTS UNIFORMLY SPACED AROUND THE PERIMETER OF |
| | THE POOL, SPA, OR HOT TUB. FOR NONCONDUCTIVE POOL |
| | SHELLS, BONDING AT FOUR POINTS SHALL NOT BE REQUIRED. |
| | |
| | 7. ALL FIXED METAL PARTS INCLUDING, BUT NOT LIMITED TO, |
| | METAL-SHEATHED CABLES AND RACEWAYS, METAL PIPING, METAL |
| | AWNINGS, METAL FENCES AND METAL DOOR AND WINDOW |
| | FRAMES.WITHIN 5 FEET (1524 MM) HORIZONTALLY FROM THE |
| | INSIDE WALLS OF THE POOL. |
| | |