2016-06-17 16:42:192ND REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 DENIED COMMENTS FROM FIRST REVIEW WERE NOT ADDRESSED AS
 FOLLOWS:
  
 PLEASE DEMONSTRATE THE EXISTENCE OF PROVIDE DETAIL TO
 ASSURE THE INSTALLATION OF AN EQUIPOTENTIAL BONDING
 GRID AT THE PERIMETER SURFACES THAT EXTEND LESS THAN 3
 FEET (914 MM) BEYOND THE INSIDE WALL OF THE POOL
  
 SECTION E4204 BONDING
  
 E4204.1 PERFORMANCE.
 THE EQUIPOTENTIAL BONDING REQUIRED BY THIS SECTION
 SHALL BE INSTALLED TO REDUCE VOLTAGE GRADIENTS IN THE
 POOL AREA AS PRESCRIBED.
  
 2. PERIMETER SURFACES. THE PERIMETER SURFACE SHALL
 EXTEND FOR 3 FEET (914 MM) HORIZONTALLY BEYOND THE
 INSIDE WALLS OF THE POOL AND SHALL INCLUDE UNPAVED
 SURFACES, POURED CONCRETE SURFACES AND OTHER TYPES OF
 PAVING. PERIMETER SURFACES THAT EXTEND LESS THAN 3 FEET
 (914 MM) BEYOND THE INSIDE WALL OF THE POOL AND THAT
 ARE SEPARATED FROM THE POOL BY A PERMANENT WALL OR
 BUILDING 5 FEET (1524 MM) OR MORE IN HEIGHT SHALL
 REQUIRE EQUIPOTENTIAL BONDING ON THE POOL SIDE OF THE
 PERMANENT WALL OR BUILDING. BONDING TO PERIMETER
 SURFACES SHALL BE PROVIDED AS SPECIFIED IN ITEM 2.1 OR
 2.2 AND SHALL BE ATTACHED TO THE POOL, SPA, OR HOT TUB
 REINFORCING STEEL OR COPPER CONDUCTOR GRID AT A MINIMUM
 OF FOUR POINTS UNIFORMLY SPACED AROUND THE PERIMETER OF
 THE POOL, SPA, OR HOT TUB. FOR NONCONDUCTIVE POOL
 SHELLS, BONDING AT FOUR POINTS SHALL NOT BE REQUIRED.
  
 7. ALL FIXED METAL PARTS INCLUDING, BUT NOT LIMITED TO,
 METAL-SHEATHED CABLES AND RACEWAYS, METAL PIPING, METAL
 AWNINGS, METAL FENCES AND METAL DOOR AND WINDOW
 FRAMES.WITHIN 5 FEET (1524 MM) HORIZONTALLY FROM THE
 INSIDE WALLS OF THE POOL.
  