| Plan Review Notes For Permit 16050286 |
| Permit Number |
16050286 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-12 08:54:47 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. SHORING/RESHORE ENGINEERING IS TO BE REVIEWED BY THE | | | ENGINEER OF RECORD, FBC 107. EITHER A SHOP DRAWING | | | REVIEW STAMP OR A LETTER IS ACCEPTABLE. IN THIS CASE, A | | | LETTER WAS PROVIDED. THE LETTER HAS BEEN ALTERED BY | | | HAND AND IS NOT SIGNED BY THE ENGINEER. IT IS NOT CLEAR | | | WHETHER OR NOT THE EOR HAS REVIEWED THE ENGINEERING. IT | | | IS ACCEPTABLE FOR ANOTHER ENGINEER IN THE OFFICE TO | | | REVIEW, BUT THE REVIEW LETTER SHOULD BE SIGNED BY THE | | | INDIVIDUAL TAKING RESPONSIBILITY FOR THE REVIEW. | | | | | | 2. PER KEN CONRAD, CHIEF BUILDING INSPECTOR, A | | | GUARDRAIL DETAIL IS REQUIRED, FBC 107. THIS MAY BE | | | SUBMITTED SEPARATELY FROM THE SHORING/RESHORE | | | ENGINEERING. IF THIS HAS ALREADY BEEN PROVIDED DIRECTLY | | | TO K.CONRAD, PLEASE ADVISE. | | | | | | |
|