| 2016-05-07 14:32:15 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16050281 |
| | ADD: 1200 S. FLAGLER DR. SUITE # 801 |
| | CONT: FOWLER BUILDING |
| | TEL: 772-486-5350 |
| | E-MAIL: [email protected] |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. MAY 07/2014 |
| | ACTION: DENIED |
| | |
| | 1) THE PLANS SUBMITTED ARE NOT DRAFTSMAN QUALITY PLANS |
| | NOR DOES THE PLAN ITSELF PROVIDE DETAILS AS REQUIRED TO |
| | BUILD BY. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS |
| | SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING |
| | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| | SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. |
| | |
| | 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE. THE |
| | BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL |
| | POLICY, OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, |
| | IN ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION |
| | PROGRAM. THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM |
| | SIZE, SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED |
| | TO RECORDS MANAGEMENT. |
| | |
| | 2) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5..1.1 COMMERCIAL BUILDINGS: |
| | FLOOR PLAN TO SCALE WITH DIMENSIONS. |
| | DETAILS FOR DROPPED CEILINGS AND SOFFITS. HOW LOW WILL |
| | THE DROPPED CEILINGS AND SOFFITS BE FROM FINISH FLOOR. |
| | WHAT FRAMING MATERIALSS WILL BE USED, WHAT SIZE OR |
| | GAUGE MATERIALS, AT WHAT CENTERS WILL THE FRAMING |
| | MEMBERS BE, HOW LONG OF SPANS WILL THE FRAMING MEMBERS |
| | NEED TO CARRY, WHAT TYPE OF FINISH MATERIALS AND |
| | THICKNEES WILL BE ON THE FRAMING MEMBERS, WHAT TYPE OF |
| | ANCHORS WILL BE USED FOR ANCHORING INTO THE WALL |
| | FRAMING AS WELL AS THE CONCRETE FLOOR CEILING ASSEMBLY. |
| | DOES THIS BUILDING HAVE A POST-TENSION CABLING FLOOR |
| | SYSTEM AND IF SO, PLEASE PROVIDE A COPY OF THE X-RAY |
| | REPORT. AT WHAT DEFLECTION HAS THE DROPPED CEILING AND |
| | OR SOFFITS BEEN DESIGNED TO AND DOES THIS SYSTEM |
| | REQUIRE A STIM BACK SYSTEM FOR THE SPANS. 107.2.1.3 |
| | ADDITIONAL INFORMATION NOT PROVIDED IN THIS REVIEW. |
| | |
| | 3) NOTED FLOOR UNDERLAYMENT WAS COMPLETED UNDER PERMIT |
| | 15090035 INSPECTED ON 10/18/15 WITH # 143 MISC. |
| | INSPECTION. NOTE A 104 FINAL WILL NEED TO BE CALLED IN |
| | OTHERWISE THIS PERMIT WILL EXPIRE AND HAVE TO BE |
| | RENEWED!!!! |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |