Plan Review Notes
Plan Review Notes For Permit 16050258
Permit Number 16050258
Review Stop P
Sequence Number 2
Notes
Date Text
2016-07-31 07:13:071) SHT. A010 - DETAIL 3 - SHOW THE MOUNTING DIMENSIONS
 OF THE HAND DRYER AND THE PAPER TOWEL DISPENSER. COMPLY
 WITH 2014 FBC-ACCESS. SEC.308, 604.9.6 THE TOILET PAPER
 DISPENSER SHALL BE LOCATED 7-9 INCHES FROM THE FRONT OF
 THE WATER CLOSET TO THE CENTER LINE OF THE DISPENSER.
 2) SHT. A010 - ONE LAVATORY OUTSIDE OF THE TOILET
 COMPARTMENT SHALL COMPLY WITH 2014 FBC-ACCESS
 SEC.213.3.4, 306 AND 606. SHOW THE REQUIRED KNEE AND
 TOE CLEARANCES ON DETAIL #6 ON SHT. A010.
 3) THE NARRATIVE RESPONSES TO THE PREVIOUS PLUMBING
 REVIEW COMMENTS STATE THAT THE GREASE INTERCEPTOR HAS
 BEEN INCREASED TO 2000 GALLONS BUT THE PLANS SHOW 750
 GALLONS. CLARIFY.
 4) THE SANITARY RISER SHOWS ITEM B2 (ICE BIN)
 DISCHARGING INTO THE GREASY WASTE SYSTEM. THIS ITEM
 SHALL DISCHARGE TO THE SANITARY PER 2014 FBC-PLUMBING
 SEC.1003.2.
 5) THE THREE COMPARTMENT SINK HAS NOT BEEN INCLUDED
 INTO THE CALCULATIONS FOR THE SIZING OF THE GREASE
 INTERCEPTOR. THIS FIXTURE MUST BE INCLUDED IN THE
 CALCULATIONS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  