| Plan Review Notes For Permit 16050258 |
| Permit Number |
16050258 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-07-31 07:13:07 | 1) SHT. A010 - DETAIL 3 - SHOW THE MOUNTING DIMENSIONS | | | OF THE HAND DRYER AND THE PAPER TOWEL DISPENSER. COMPLY | | | WITH 2014 FBC-ACCESS. SEC.308, 604.9.6 THE TOILET PAPER | | | DISPENSER SHALL BE LOCATED 7-9 INCHES FROM THE FRONT OF | | | THE WATER CLOSET TO THE CENTER LINE OF THE DISPENSER. | | | 2) SHT. A010 - ONE LAVATORY OUTSIDE OF THE TOILET | | | COMPARTMENT SHALL COMPLY WITH 2014 FBC-ACCESS | | | SEC.213.3.4, 306 AND 606. SHOW THE REQUIRED KNEE AND | | | TOE CLEARANCES ON DETAIL #6 ON SHT. A010. | | | 3) THE NARRATIVE RESPONSES TO THE PREVIOUS PLUMBING | | | REVIEW COMMENTS STATE THAT THE GREASE INTERCEPTOR HAS | | | BEEN INCREASED TO 2000 GALLONS BUT THE PLANS SHOW 750 | | | GALLONS. CLARIFY. | | | 4) THE SANITARY RISER SHOWS ITEM B2 (ICE BIN) | | | DISCHARGING INTO THE GREASY WASTE SYSTEM. THIS ITEM | | | SHALL DISCHARGE TO THE SANITARY PER 2014 FBC-PLUMBING | | | SEC.1003.2. | | | 5) THE THREE COMPARTMENT SINK HAS NOT BEEN INCLUDED | | | INTO THE CALCULATIONS FOR THE SIZING OF THE GREASE | | | INTERCEPTOR. THIS FIXTURE MUST BE INCLUDED IN THE | | | CALCULATIONS. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|