| Plan Review Notes For Permit 16050258 |
| Permit Number |
16050258 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-07-15 16:40:50 | 2ND REVIEW MECHANICAL | | | PERMIT #16050258 | | | 7/15/16 | | | | | | 1) PREVIOUS BUILDING REVIEW COMMENTS REGARDING ACCESS | | | TO SERVICEABLE MECHANICAL EQUIPMENT ON ROOF TOPS HAS | | | NOT BEEN COMPLETELY RESOLVED. SEE SHEET A008 AND REFER | | | TO SECTION 306.5: INDICATE HOW ACCESS TO THE KITCHEN | | | EXHAUST AND SUPPLY FANS ON THE SLOPED ROOF WILL BE | | | ACCOMPLISHED, AND PROVIDE THE SLOPE OF THE ROOF. AS THE | | | KITCHEN EXHAUST HOOD WILL BE UNDER SEPARATE PERMIT, | | | THIS CAN BE CONSIDERED AN "ADVISORY COMMENT" HOWEVER IT | | | IS RECOMMENDED THAT THESE ISSUES BE RESOLVED PRIOR TO | | | APPROVAL OF THE MAIN CONSTRUCTION PLANS. | | | | | | 2) CONTRARY TO THE ARCHITECT'S NARRATIVE RESPONSE | | | REGARDING WIND LOAD ENGINEERING FOR THE ROOFTOP | | | MECHANICAL EQUIPMENT, THE REQUESTED WIND LOAD DESIGN | | | CRITERIA AND INSTALLATION DETAILS ARE INCOMPLETE, AND | | | THE EOR IS STATING IN NOTE #21 ON SHEET M001, IT WILL | | | BE PROVIDED BY A DELEGATED STRUCTURAL ENGINEER. PLEASE | | | CLARIFY IF THE DELEGATED ENGINEERING IS TO BE SUBMITTED | | | WITH THE MAIN PLANS FOR PERMITTING, OR ARE YOU | | | REQUESTING A DEFERRED SUBMITTAL? | | | | | | 3) THE DIGITAL SIGNATURE FOR THE ENERGY CALCULATIONS | | | HAS A PROCESS ERROR. | | | | | | 4) PLACE A NOTE INDICATING THAT THE EXTERIOR WALK-IN | | | BOXES AND REFRIGERATION WILL BE DONE UNDER SEPARATE | | | PERMIT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|