Plan Review Notes
Plan Review Notes For Permit 16050258
Permit Number 16050258
Review Stop G
Sequence Number 2
Notes
Date Text
2016-07-31 07:32:44GAS
 1) SHT. P-005 REFERS TO THE 2007 FBC. THE CODE IN
 EFFECT IS THE 2014 FBC. REVISE THE NOTE.
 2) A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR PER 2014 FBC-GAS
 SEC.409.4.
 3) A TEE FITTING WITH ONE END PLUGGED OR CAPPED SHALL
 BE INSTALLED BETWEEN THE MP REGULATOR AND ITS UPSTREAM
 SHUTOFF VALVE. THE FITTING SHALL BE POSITIONED TO ALLOW
 CONNECTION OF A PRESSURE-MEASURING DEVICE. 2014 FBC-GAS
 SEC.410.2 (5).
 4) A TEE FITTING COMPLYING WITH 2014 FBC-GAS SEC.410.2
 (6) SHALL BE INSTALLED.
 5) SHT. P005 -NOTE #6 REGERS TO BELOW SLAB
 PIPING.PIPING INSTALLED UNDER A SLAB INSIDE THE
 BUILDING IS PROHIBITED PER THE 2014 FBC-GAS SEC.404.6.
 IF NOTE #6 IS MEANT TO REFER TO UNDERGROUND PIPING,
 PLEASE REVISE THE NOTE.
  