| Plan Review Notes For Permit 16050258 |
| Permit Number |
16050258 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-07-31 07:32:44 | GAS | | | 1) SHT. P-005 REFERS TO THE 2007 FBC. THE CODE IN | | | EFFECT IS THE 2014 FBC. REVISE THE NOTE. | | | 2) A LISTED SHUTOFF VALVE SHALL BE INSTALLED | | | IMMEDIATELY AHEAD OF EACH MP REGULATOR PER 2014 FBC-GAS | | | SEC.409.4. | | | 3) A TEE FITTING WITH ONE END PLUGGED OR CAPPED SHALL | | | BE INSTALLED BETWEEN THE MP REGULATOR AND ITS UPSTREAM | | | SHUTOFF VALVE. THE FITTING SHALL BE POSITIONED TO ALLOW | | | CONNECTION OF A PRESSURE-MEASURING DEVICE. 2014 FBC-GAS | | | SEC.410.2 (5). | | | 4) A TEE FITTING COMPLYING WITH 2014 FBC-GAS SEC.410.2 | | | (6) SHALL BE INSTALLED. | | | 5) SHT. P005 -NOTE #6 REGERS TO BELOW SLAB | | | PIPING.PIPING INSTALLED UNDER A SLAB INSIDE THE | | | BUILDING IS PROHIBITED PER THE 2014 FBC-GAS SEC.404.6. | | | IF NOTE #6 IS MEANT TO REFER TO UNDERGROUND PIPING, | | | PLEASE REVISE THE NOTE. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|