2016-05-31 11:47:42PLUMBING NOTES:
  
 1. GRAB BARS SHALL BE MEASURED FROM FINISHED FLOOR TO
 TOP OF GRIPING SURFACE AT A MIN. OF 33IN. AND MAX. OF
 36IN. PER FBC ACC. SEC. 609.4
  
 2. PLEASE SHOW CLEARANCE FOR TOILET SHALL COMPLY WITH
 FBC ACC. SEC. 604.8.1.1 SIZE.
 WHEELCHAIR ACCESSIBLE COMPARTMENTS SHALL BE 60 INCHES
 (1525 MM) WIDE MINIMUM MEASURED PERPENDICULAR TO THE
 SIDE WALL, AND 56 INCHES (1420 MM) DEEP MINIMUM FOR
 WALL HUNG WATER CLOSETS AND 59 INCHES (1500 MM) DEEP
 MINIMUM FOR FLOOR MOUNTED WATER CLOSETS MEASURED
 PERPENDICULAR TO THE REAR WALL. WHEELCHAIR ACCESSIBLE
 COMPARTMENTS FOR CHILDREN?S USE SHALL BE 60 INCHES
 (1525 MM) WIDE MINIMUM MEASURED PERPENDICULAR TO THE
 SIDE WALL, AND 59 INCHES (1500 MM) DEEP MINIMUM FOR
 WALL HUNG AND FLOOR MOUNTED WATER CLOSETS MEASURED
 PERPENDICULAR TO THE REAR WALL.
  
 3. SHOW CLEAR FLOOR SPACE FOR LAVATORY PER FBC ACC.
 SEC. 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 4. SHOW CLEAR FLOOR SPACE FOR ACCESSIBLE URINAL.
 PER FBC ACC. SEC 605.3 CLEAR FLOOR SPACE.
 A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305
 POSITIONED FOR FORWARD APPROACH SHALL BE PROVIDED.
  
 5. HEIGHT OF TOILET SEAT SHALL COMPLY WITH FBC ACC.
 SEC. 604.4 SEATS.
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
  
 6. PROVIDE OCCUPANT LOAD ON PLAN. PER WPB AMEND. TO FBC
 SEC. 107.2.1
  
 7. 016 SHT..2 EXFILTRATION TRENCH, SHOWS PIPE SIZE AND
 TRENCH SIZE AS VARIES 015 SHT.1 DETAIL FOR EXFILTRATION
 TRENCH SHOWS A SIZE PLEASE CLARIFY. PER WPB AMEND. TO
 FBC SEC. 107.2.1
  
 8. USE STANDARD DETAIL GS-7 FROM WPB UTILITIES FOR
 GRAVITY GREASE INTERCEPTOR AND SHOW 6IN. SAMPLING PORT
 ON PLAN. PER WPB AMEND. TO FBC SEC. 107.2.1
  
 9. RECIRCULATING SYSTEM MAYBE REQUIRED TO COMPLY WITH
 FBC PL. SEC. 607.2 HOT OR TEMPERED WATER SUPPLY TO
 FIXTURES.
 THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING,
 FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT
 REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET
 (15 240 MM). RECIRCULATING SYSTEM PIPING AND
 HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF
 HOT OR TEMPERED WATER
  
 10. SOME OF THE SIZING IS MISSING IN THE GREASE SYSTEM
 IN KITCHEN PLEASE PROVIDE . PER WPB AMEND. TO FBC SEC.
 107.2.1
  
 11. GREASE INTERCEPTOR SIZING CALCULATIONS ARE
 INCOMPLETE FOR A GRAVITY TANK YOU HAVE TO MULTIPLY THE
 65 GPM BY 30 MIN. RETENTION TIME WITCH GIVES YOU 1950
 GAL MIN TANK CAPACITY THE 750 WILL BE TO SMALL YOU WILL
 HAVE TO USE A 2000 GAL. GRAVITY TANK.
  
 DO TO PLANS BEING INCOMPLETE OR UNCLEAR, A
 COMPREHENSIVE PLAN REVIEW CANNOT BE DONE AT THIS TIME,
 THERE MAYBE ADDITIONAL COMMENTS ON RESUBMITTAL OF
 PLANS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH