2016-06-01 16:39:591ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16050258
 6/1/16
  
 1) SUBMIT ENERGY CALCULATIONS IN COMPLIANCE WITH
 SECTIONS C101.4.4 & C401.2 FBC-14 ENERGY CONSERVATION.
  
 2) THE AC CALCULATIONS ON SHEET M006 DO NOT INCLUDE THE
 HEATING LOAD, DO NOT INCLUDE A SPACE LOAD FOR THE
 KITCHEN, DO NOT SHOW A TOTAL LATENT LOAD, AND DO NOT
 APPEAR TO BE PERFORMED IN ACCORDANCE WITH THE
 ASHRAE/ACCA STANDARD 183 OR ACCA MANUAL N. PLEASE
 CLARIFY WHAT PROCESSES ARE CONTRIBUTING TO THE "PROCESS
 LOADS" SHOWN IN THE CALCS.
  
 3) REFER TO SECTION C403.2.2: RTU 1 & 2 PER THE
 SCHEDULE HAVE A COMBINED TOTAL CAPACITY OF 30 TONS
 (360,000 BTUH) WHICH EXCEEDS THE TOTAL 241,000 BTUH
 LOAD IN THE CALCULATION.
  
 4) PROVIDE THE WIND LOAD DESIGN CRITERIA AND
 ENGINEERING FOR INSTALLATION OF THE RTU'S AND THE
 EXTERIOR DUCTWORK- SECTION 301.15.
  
 5) SHEET M004: PROVIDE DETAILS FOR INSTALLATION OF THE
 GUARDRAIL SHOWN ON THE ROOF BY THE RTU'S- SEE SECTION
 304.11.
  
 6) SHUTOFF DAMPER CONTROLS FOR THE O/A SUPPLY ARE
 REQUIRED PER SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION.
  
 7) DEMAND CONTROLLED VENTILATION IS REQUIRED FOR THE
 DINING ROOM- SECTION C403.2.5.1. REVISE THE PLAN TO
 SHOW COMPLIANCE.
  
 8) INDICATE THE TYPE OF EXTERIOR DUCTWORK TO BE
 INSTALLED AND THE INSULATION R-VALUE.
  
 9) PROVIDE A CONDENSATE DISPOSAL PLAN- SECTION 307.
  
 CHRISTOPHER L. COLE