2016-05-31 13:31:56GAS COMMENTS:
  
 1. PROVIDE LENGTH OF EACH CUT SECTION OF PIPE ON
 ISOMETRIC DRAWING. PER FBC FG SEC. 402.4.1-402.4.2
  
 2.THE NOTE FOR YOUR 2PSI SYSTEM INDICATES TABLE
 402.4(18) WHICH IS CSST ON THE ISOMETRIC DRAWING YOUR
 REFERENCING BS PIPE WHAT DOES BS STAND FOR PLEASE
 CLARIFY WHAT TYPE OF PIPE YOU USING. PER WPB AMEND. TO
 FBC SEC. 107.2.1
  
 3. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 4.SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 5. IN THE NOTES FOR THE GAS PIPING YOU ARE REFERENCING
 BS PIPING AND SLEEVING PIPING UNDER THE SLAB , THE
 ISOMETRIC DRAWING DOES NOT SHOW ANY PIP UNDER THE SLAB
 PLEASE CLARIFY . PLEASE REMOVE ANY NOTES THAT DO NOT
 APPLY TO THIS GAS SYSTEM. PER WPB AMEND. TO FBC SEC.
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
 DO TO PLANS BEING INCOMPLETE OR UNCLEAR, A
 COMPREHENSIVE PLAN REVIEW CANNOT BE DONE AT THIS TIME,
 THERE MAYBE ADDITIONAL COMMENTS ON RESUBMITTAL OF
 PLANS.
  
  