Plan Review Notes
Plan Review Notes For Permit 16050258
Permit Number 16050258
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-05-24 13:34:08THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A002 - THERE IS INDICATIONS OF CODE COMPLIANT
 EXITS FROM THE OUTSIDE SEATING THROUGHOUT THE OUTDORR
 AREA. THERE IS INDICATIONS OF A DOUBLE DOOR GATE AT THE
 FRONT OF THE OUTDOOR AREA. NO REAR DOOR/GATE IS
 INDICATED. EXITING THROUGH THE DUMPSTER ENCLOSURE IS
 PROHIBITED.PLEASE PROVIDE TWO COMPLIANT EXIT DOOR/GATES
 WITH APPROPRIATE EXITING HARDWARE PER NFPA 101, CHAPTER
 12 & CHAPTER 7
 12.2.4* NUMBER OF MEANS OF EGRESS.
 12.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH SECTION 7.4, OTHER THAN EXITS FOR
 FENCED OUTDOOR ASSEMBLY OCCUPANCIES IN ACCORDANCE WITH
 12.2.4.4.
 12.2.4.4 A FENCED OUTDOOR ASSEMBLY OCCUPANCY SHALL HAVE
 NOT LESS THAN TWO REMOTE MEANS OF EGRESS FROM THE
 ENCLOSURE IN ACCORDANCE WITH 7.5.1.3, UNLESS OTHERWISE
 REQUIRED BY ONE OF THE FOLLOWING:
 (1) IF MORE THAN 6000 PERSONS ARE TO BE SERVED BY SUCH
 MEANS OF EGRESS, THERE SHALL BE NOT LESS THAN THREE
 MEANS OF EGRESS.
 (2) IF MORE THAN 9000 PERSONS ARE TO BE SERVED BY SUCH
 MEANS OF EGRESS, THERE SHALL BE NOT LESS THAN FOUR
 MEANS OF EGRESS.
  
  
  
 2) SHEET A011 - PER FLORIDA 69A-60.0081; NOTICE SIGNAGE
 IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY
 MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE
 WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH A MALTESE CROSS SIGN MEASURING 8 INCHES
 HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED
 REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED
 WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR.
 A. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 B. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 C. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
  
 3) SHEET A013 - DOOR LOCKS ON EXIT DOORS SHALL COMPLY
 WITH NFPA 101 CHAPTER 12 & CHAPTER 7.
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS
 SHALL BE PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK
 ONLY IF THE LATCH OR LOCK IS PANIC HARDWARE OR FIRE
 EXIT HARDWARE COMPLYING WITH 7.2.1.7, UNLESS OTHERWISE
 PERMITTED BY ONE OF THE FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 LOCKS AS PERMITTED IN 12.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO
 ACCESS-CONTROLLED EGRESS DOORS AS PERMITTED IN
 12.2.2.2.6. 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH
 7.2.1.5.5 SHALL BE PERMITTED TO BE USED ON A SINGLE
 DOOR OR A SINGLE PAIR OF DOORS IF BOTH OF THE FOLLOWING
 CONDITIONS APPLY:
 (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT
 AND THE ASSEMBLY OCCUPANCY HAS AN OCCUPANT LOAD NOT
 GREATER THAN 500.
 (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN
 ASSEMBLY OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR
 MORE ARE RELEASED BY PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
  
 7.2.1.7 PANIC HARDWARE AND FIRE EXIT HARDWARE.
 7.2.1.7.1 WHERE A DOOR ASSEMBLY IS REQUIRED TO BE
 EQUIPPED WITH PANIC OR FIRE EXIT HARDWARE, SUCH
 HARDWARE SHALL MEET ALL OF THE FOLLOWING CRITERIA:
 (1) IT SHALL CONSIST OF A CROSS BAR OR A PUSH PAD, THE
 ACTUATING PORTION OF WHICH EXTENDS ACROSS NOT LESS THAN
 ONE-HALF OF THE WIDTH OF THE DOOR LEAF.
 (2) IT SHALL BE MOUNTED AS FOLLOWS:
 (A) NEW INSTALLATIONS SHALL BE NOT LESS THAN 34 IN.
 (865 MM), AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE
 FLOOR.
 (B) EXISTING INSTALLATIONS SHALL BE NOT LESS THAN 30
 IN. (760 MM), AND NOT MORE THAN 48 IN. (1220 MM), ABOVE
 THE FLOOR.
 (3) IT SHALL BE CONSTRUCTED SO THAT A HORIZONTAL FORCE
 NOT TO EXCEED 15 LBF (66 N) ACTUATES THE CROSS BAR OR
 PUSH PAD AND LATCHES.
 7.2.1.7.2 ONLY APPROVED PANIC HARDWARE SHALL BE USED ON
 DOOR ASSEMBLIES THAT ARE NOT FIRE-RATED DOOR
 ASSEMBLIES. ONLY APPROVED FIRE EXIT HARDWARE SHALL BE
 USED ON FIRE-RATED DOOR ASSEMBLIES. NEW PANIC HARDWARE
 AND NEW FIRE EXIT HARDWARE SHALL COMPLY WITH ANSI/UL
 305, STANDARD FOR SAFETY PANIC HARDWARE, AND ANSI/BHMA
 A156.3, EXIT DEVICES.
 7.2.1.7.3 REQUIRED PANIC HARDWARE AND FIRE EXIT
 HARDWARE, IN OTHER THAN DETENTION AND CORRECTIONAL
 OCCUPANCIES AS OTHERWISE PROVIDED IN CHAPTERS 22 AND
 23, SHALL NOT BE EQUIPPED WITH ANY LOCKING DEVICE, SET
 SCREW, OR OTHER ARRANGEMENT THAT PREVENTS THE RELEASE
 OF THE LATCH WHEN PRESSURE IS APPLIED TO THE RELEASING
 DEVICE.
  
  
  
 4) SHEET E001 - THERE IS NO INDICATIONS OF A FIRE ALARM
 SYSTEM. A FIRE ALARRM SYSTEM IS REQUIRED WITH A
 PRELIMINARY SYSTEM SUBMITTED BY THE ENGINEER OF RECORD
 WITH A NOTE FOR SHOP DRAWINGS UNDER SEPOARATE PERMIT.
 12.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 12.3.4.1 GENERAL.
 12.3.4.1.1 ASSEMBLY OCCUPANCIES WITH OCCUPANT LOADS OF
 MORE THAN 300 AND ALL THEATERS WITH MORE THAN ONE
 AUDIENCE-VIEWING ROOM SHALL BE PROVIDED WITH AN
 APPROVED FIRE ALARM SYSTEM IN ACCORDANCE WITH 9.6.1 AND
 12.3.4, UNLESS OTHERWISE PERMITTED BY 12.3.4.1.2.
  
  
 5) SHEET E006 - IT IS RECOMMENDED THAT THE EXIT LIGHTS
 INDICATED ALONG THE EAST WALL AT THE CENTER AND FRONT
 LOCATION BE ONLY EMERGENCY LIGHTS WITHOUT EXIT WORDING
 OR ARROW INDICATORS. TOO MANY EXIT SIGNS MAY CONFUSE
 THE OCCUPANTS IN SUCH A LARGE OPEN AREA AND HAVING THE
 EXIT SIGNS NEAREST THE ACTUAL EXIT MAY ASSIST IN
 LEADING THE OCCUPANT TO THE NEAREST EXIT.
 7.10.2 DIRECTIONAL SIGNS.
 7.10.2.1* A SIGN COMPLYING WITH 7.10.3, WITH A
 DIRECTIONAL INDICATOR SHOWING THE DIRECTION OF TRAVEL,
 SHALL BE PLACED IN EVERY LOCATION WHERE THE DIRECTION
 OF TRAVEL TO REACH THE NEAREST EXIT IS NOT APPARENT.
  
  
 6) SHEET E006 - THERE IS AN EXIT SIGN INDICATED
 DIRECTLY IN FRONT OF THE OFFICE DOOR. IT IS RECOMMENDED
 TO MOVE THIS EXIT LIGHT TO THE EAST INTO THE OPEN AREA
 AND AWAY FROM THE OFFICE DOOR.
  
  
 7) SHEET E001 THRU E011 - THERE IS NO INDICATION OF ANY
 EMERGENCY LIGHTING, ILLUMINATION OF THE MEANS OF EGRESS
 AND EXIT SIGNS IN THE OUTDOOR AREA. PLEASE PROVIDE PER
 NFPA 101, CHAPTER 7, MEANS OF EGRESS.
  
 8) SHEET FP003 - THERE ARE NO FIRE SPRINKLERS INDICATED
 UNDER THE EXTERIOR ATTACHED CANVAS CANOPY. THE FIRE
 SPRINKLER SYSTEM SHALL BE EXTENDED TO UNDER THE CANOPY,
 BY PENDENT OR SIDEWALL PER THE ENGINEER OF RECORD.
 12.3.5.2 ANY BUILDING CONTAINING ONE OR MORE ASSEMBLY
 OCCUPANCIES WHERE THE AGGREGATE OCCUPANT LOAD OF THE
 ASSEMBLY OCCUPANCIES EXCEEDS 300 SHALL BE PROTECTED BY
 AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 9.7 AS FOLLOWS (SEE ALSO
 12.1.6, 12.2.6, 12.3.2, AND 12.3.6):
 (1) THROUGHOUT THE STORY CONTAINING THE ASSEMBLY
 OCCUPANCY
 (2) THROUGHOUT ALL STORIES BELOW THE STORY CONTAINING
 THE ASSEMBLY OCCUPANCY
 (3) IN THE CASE OF AN ASSEMBLY OCCUPANCY LOCATED BELOW
 THE LEVEL OF EXIT DISCHARGE, THROUGHOUT ALL STORIES
 INTERVENING BETWEEN THAT STORY AND THE LEVEL OF EXIT
 DISCHARGE, INCLUDING THE LEVEL OF EXIT DISCHARGE
  
  
 9) SHEET FP003 - THERE IS NO INDICATION OF ANY FIRE
 SPRINKLER PROTECTION UNDER THE EXTERIOR FRAME AND ROOF
 AREA SUPPERTING THE A/C MECHANICAL EQUIPMENT. THE FIRE
 SPRINKLER SYSTEM SHALL BE EXTENDED TO UNDER THE
 DECKING, BY PENDENT OR SIDEWALL PER THE ENGINEER OF
 RECORD.
  
  
 10) PROVIDE A NOTE INDICATING THAT THE CANVAS CANOPY
 SHALL BE UNDER SEPARATE PERMIT AND SHALL INCLUDE FLAME
 RETARDENT FABRIC.
  
  
 11) SHEET A002 - INDICATES WALKIN COOLERS UNDER THE
 OUTSIDE DECKING. NO DETAIL IS PROVIDED, INCLUDING
 LIGHTING, EMERGENCY LIGHTING, FIRE ALRM OF FIRE
 SPRINKLER PROTECTION. THE SITE PLALN ALSO INDICATES A
 WOOD DECK WALK WAY THAT LEADS THROUGH THIS AREA THAT
 MAY BE AN EGRESS TRAVEL PATH THAT IS REQUIRED TO MEET
 NFPA 101, CHAPTER 7, MEANS OF EGRESS REQUIRERMENTS.
 PLEASE REVIEW AND PROVIDE REQUIRED DIMENSIONS, HEIGHT &
 WIDTH, SIGNAGE, AND ILLUMINATION.
  
  
 12) THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
  
 13) THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  