2016-06-20 09:43:54INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. GENERAL NOTES- PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS
 FOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED
 TO FIRE ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA,
 SIGNAGE, WIRELESS SYSTEMS A NOTE WILL SUFFICE.
 2. PLEASE ADDRESS ALL FIRE COMMENTS RELATED TO
 ELECTRICAL SCOPE, OUTDOOR LIGHTING AND MEANS OF EGRESS.
 FBC 107.3.5
 3. SERVICE HAS BEEN REVISED COMPLETELY, PROVIDE FROM
 UTILITY PROVIDER (FPL), ACTUAL AVAILABLE FAULT CURRENT
 AT THE TRANSFORMERS. FBC 107.3.5
 4. PROVIDE AIC CALCULATION PER NEC 110.10- FBC 107.3.5
 5. PROVIDE A NOTE/SIGN TO INDICATE THE REQUIREMENTS NEC
 110.24 THE MAX. AVAILABLE FAULT CURRENT SHALL BE
 DURABLY MARKED AND DATED ON ALL ELECTRICAL APPARATUS
 AND NEC 110.16 ARC-FLASH HAZARD WARNING LABELS
 REQUIRED.
 6. PER FBC EC 405.7.3- SHOW VOLTAGE DROP CALCULATIONS
 FOR FEEDERS AND BRANCH CIRCUITS.
 7. CLARIFY IF SERVICE UNFUSED CONDUCTORS ARE IN THE
 INTERIOR OF BUILDING, IF SO AHJ WILL LIMIT LENGTH OF
 UNFUSED CONDUCTORS. MAX 8FT OF CONDUCTOR LENGTH WILL BE
 ALLOWED.
 8. CLARIFY IF CIRCUIT P1-13 IS FOR THE REQUIRED SHOW
 WINDOW RECEPTACLES PER NEC 2210.62
 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  