| 2016-06-20 09:43:54 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 NEC |
| | COMMENTS: |
| | |
| | 1. GENERAL NOTES- PROVIDE A BLOCK NOTE INDICATING THE |
| | REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS |
| | FOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED |
| | TO FIRE ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA, |
| | SIGNAGE, WIRELESS SYSTEMS A NOTE WILL SUFFICE. |
| | 2. PLEASE ADDRESS ALL FIRE COMMENTS RELATED TO |
| | ELECTRICAL SCOPE, OUTDOOR LIGHTING AND MEANS OF EGRESS. |
| | FBC 107.3.5 |
| | 3. SERVICE HAS BEEN REVISED COMPLETELY, PROVIDE FROM |
| | UTILITY PROVIDER (FPL), ACTUAL AVAILABLE FAULT CURRENT |
| | AT THE TRANSFORMERS. FBC 107.3.5 |
| | 4. PROVIDE AIC CALCULATION PER NEC 110.10- FBC 107.3.5 |
| | 5. PROVIDE A NOTE/SIGN TO INDICATE THE REQUIREMENTS NEC |
| | 110.24 THE MAX. AVAILABLE FAULT CURRENT SHALL BE |
| | DURABLY MARKED AND DATED ON ALL ELECTRICAL APPARATUS |
| | AND NEC 110.16 ARC-FLASH HAZARD WARNING LABELS |
| | REQUIRED. |
| | 6. PER FBC EC 405.7.3- SHOW VOLTAGE DROP CALCULATIONS |
| | FOR FEEDERS AND BRANCH CIRCUITS. |
| | 7. CLARIFY IF SERVICE UNFUSED CONDUCTORS ARE IN THE |
| | INTERIOR OF BUILDING, IF SO AHJ WILL LIMIT LENGTH OF |
| | UNFUSED CONDUCTORS. MAX 8FT OF CONDUCTOR LENGTH WILL BE |
| | ALLOWED. |
| | 8. CLARIFY IF CIRCUIT P1-13 IS FOR THE REQUIRED SHOW |
| | WINDOW RECEPTACLES PER NEC 2210.62 |
| | 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE |
| | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING |
| | THIS PROJECT. |
| | |
| | |
| | VALENTINO PEREZ |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |