Plan Review Notes
Plan Review Notes For Permit 16050258
Permit Number 16050258
Review Stop B
Sequence Number 1
Notes
Date Text
2016-06-07 16:42:49BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16050258
 ADD: 209 6TH ST.
 CONT: OWNER BUILDER ALLIANCES
 TEL: 561-254-6779
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JUNE 07/2016
 ACTION: DENIED
  
 1) SHEET 001-A001 TITLE SHEET:
 1A) THE TITLE SHEET DOES NOT PROVIDE THE ACTUAL
 OCCUPANT LOAD FOR THE MERCANTILE MEAT MARKET, OR THE
 OCCUPANT LOAD FOR THE INTERIOR A2 ASSEMBLY SEATING,
 KITCHEN AND SUPPLY AREAS. ALSO INCLUDE UNDER A SEPARATE
 HEADING THE OCCUPANT LOAD FOR THE EXTERIOR SEASONAL
 SEATING. 2014 FBC-B TABLE 1004.1.2.
  
 1B) TYPE V CONSTRUCTION FIRE RESISTANT RATING
 REQUIREMENTS FOR BUILDING ELEMENTS 2014 FBC-B TABLE 601
 FOR EXTERIOR WALLS 0 HR. PLEASE UPDATE CODE REFERENCE
 WITH THE REQUIREMENTS OF FOOTNOTE F & G.
 FOOTNOTE F- NOT LESS THAN THE FIRE RESISTANCE RATING
 BASED ON FIRE SEPARATION DISTANCE (SEE TABLE 602).
 WEST WALL/ EXTERIOR BEARING WALL 0-5 FEET OCCUPANCY A &
 M REQUIRES A 1 HOUR FIRE RESISTANCE RATING.
  
 2) SHEET A004 THE FLOOR PLAN NOR SHEET A005 THE
 EQUIPMENT PLAN & SCHEDULE SHOW THE LIFE SAFETY PLAN.
 THE INDEX DOES NOT SHOW A LIFE SAFETY PLAN. PLEASE
 PROVIDE COMPLIANCE WITH:
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1.1 COMMERCIAL BUILDINGS:
 (7) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT
 EXIT DISCHARGE
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
  
 3) SHEET A004 THE FLOOR PLAN NOR SHEET A005 THE
 EQUIPMENT PLAN SHOW COMPLIANCE WITH 2014 FBC-ACCESS.
 CODE 226.1 GENERAL. WHERE DINING SURFACES ARE PROVIDED
 FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST 5
 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
  
 4) SHEET A004 THE FLOOR PLAN NOR SHEET A005 THE
 EQUIPMENT PLAN SHOW COMPLIANCE WITH 2014 FBC-ACCESS.
 CODE 226.2 DISPERSION. DINING SURFACES REQUIRED TO
 COMPLY WITH 902 SHALL BE DISPERSED THROUGHOUT THE SPACE
 OR FACILITY CONTAINING DINING SURFACES. THIS INCLUDES
 BAR AREAS AS WELL AS EXTERIOR SEASONAL SEATING AS WELL.
  
 5) SHEET A004 THE FLOOR PLAN NOR SHEET A005 THE
 EQUIPMENT PLAN SHOW COMPLIANCE WITH 2014 FBC-ACCESS.
 CODE. THE PLANS ARE DEFICIENT IN SHOWING COMPLIANCE
 WITH THE MEAT MARKET COUNTERS:
 ACCESS. CODE 227.3 COUNTERS. WHERE PROVIDED, AT LEAST
 ONE OF EACH TYPE OF SALES COUNTER AND SERVICE COUNTER
 SHALL COMPLY WITH 904.4. WHERE COUNTERS ARE DISPERSED
 THROUGHOUT THE BUILDING OR FACILITY, COUNTERS COMPLYING
 WITH 904.4 ALSO SHALL BE DISPERSED.
  
 6) SHEET A004 THE FLOOR PLAN NOR SHEET A005 THE
 EQUIPMENT PLAN WILL NEED TO SHOW COMPLIANCE WITH:
 2014 FBC-ACCESS. CODE 902.1DINING SURFACES AND WORK
 SURFACES SHALL COMPLY WITH 902.2 AND 902.3.
  
 6A) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 6B) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK
 SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34
 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 7) SHEET 010-A010 INDICATES GRAB BARS BEING MEASURED
 FROM THE CENTERLINE. UNDER THE 2014 ACCESS. CODE THIS
 MEASUREMENT IS TO BE TAKEN FROM THE TOP OF THE
 GRASPABLE SURFACE. 2014 ACCESS. CODE
 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES (840 MM)
 MINIMUM AND 36 INCHES (915 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE.
 8) SHEET 010-A010 BOTTOM LEFT UNDER THE HEADING LEGEND
 FOR LAVATORIES THE HEIGHT MUST BE : 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 9) SHEET 018_S1 HAS A CHART FOR COMPONENTS AND CLADDING
 ZONES 1-5. PLEASE INDICATE IF THIS CHART IS IN VULT OR
 VASD.
 10) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) STOREFRONTS, WALL LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS,
 ROOF TOP INTAKE AND EXHAUST FANS
  
 11) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 12) FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM
 MATERIAL PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED
 TO RESIST THE OVERTURNING EFFECTS CAUSED BY THE LATERAL
 FORCES SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR
 WIND LOADS?
  
 13) SHEET 021_S4 DETAIL # 6 INDICATES THE ANCHORING OF
 WOOD TRUSSES TO THE EXTERIOR WALL THROUGH A 3X12 WOOD
 LEDGER. THE PLANS DO NOT INDICATE IF THIS WALL AT THIS
 ELEVATION IS HOLLOW CONCRETE BLOCK OR A CONCRETE TIE
 BEAM. THE DETAIL INDICATES THE USE OF ? INCH EXP. BOLTS
 BUT DOES NOT PROVIDE AT WHAT LENGTH THE EXPANSION BOLTS
 NEED TO BE SINCE THERE IS A 3 INCH LEDGER? 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 14) SHEET 019_S2 SHOWS THE MECHANICAL SCREEN SEE DETAIL
 #9 ON S-3. THIS DETAIL SHOWS 2 X6 WOOD BATTENS AND 6X6
 WOOD POST. THE DISTANCE TO THE PROPERTY LINE MEASURES 4
 FOOT 10 INCHES. TABLE 602 FIRE SEPARATION DISTANCE
 REQUIRES A 1 HOUR FIRE RATING ON THIS SCREEN WALL. SEE:
 FBC-B ? 1509.6 MECHANICAL EQUIPMENT SCREENS. MECHANICAL
 EQUIPMENT SCREENS SHALL BE CONSTRUCTED OF THE MATERIALS
 SPECIFIED FOR THE EXTERIOR WALLS IN ACCORDANCE WITH THE
 TYPE OF CONSTRUCTION OF THE BUILDING. WHERE THE FIRE
 SEPARATION DISTANCE IS GREATER THAN 5 FEET (1524 MM),
 MECHANICAL EQUIPMENT SCREENS SHALL NOT BE REQUIRED TO
 COMPLY WITH THE FIRE-RESISTANCE RATING REQUIREMENTS.
  
 15) THE HEIGHT OF THE SCREEN WALL IS GIVEN AS 18 FEET
 TALL. PLEASE SHOW HOW COMPLIANCE WITH FBC-B 1509.6.4
 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED
 STRUCTURES WILL BE ACHIEVED. WHERE EQUIPMENT AND
 APPLIANCES REQUIRING ACCESS ARE INSTALLED ON ROOFS OR
 ELEVATED STRUCTURES AT A HEIGHT EXCEEDING 16 FEET (4877
 MM), SUCH ACCESS SHALL BE PROVIDED BY A PERMANENT
 APPROVED MEANS OF ACCESS, THE EXTENT OF WHICH SHALL BE
 FROM GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND
 APPLIANCES? LEVEL SERVICE SPACE. SUCH ACCESS SHALL NOT
 REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30
 INCHES (762 MM) HIGH OR WALKING ON ROOFS HAVING A SLOPE
 GREATER THAN 4 UNITS VERTICAL IN 12 UNITS HORIZONTAL
 (33-PERCENT SLOPE).
  
 16) WITH THE NEW ELEVATED AIR HANDIER STRUCTURE PLEASE
 PROVIDE WHAT THE SAFE MINIMUM BEARING VALUE FOR THIS
 STRUCTURE. SHEET 018_S1 FOUNDATION NOTE # 1 THE
 CONTRACTOR SHALL ENGAGE A QUALIFIED GEOTECHNICAL
 ENGINEER TO VERIFY THAT THE SOILS EXCHANGE AND PAD
 COMPACTION HAVE BEEN ACCOMPLISHED IN ACCORDANCE WITH
 THE REQUIREMENTS OF THE GEOTECHNICAL REPORT. NO SOILS
 REPORT WAS SUBMITTED.
 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 17) CHANGE OF OCCUPANCY EXIST. BUILDING CODE SECTION
 1013 ENERGY CONSERVATION SEE THE FLORIDA BUILDING CODE,
 ENERGY CONSERVATION. NO DOCUMENTS WERE SUBMITTED FOR
 COMPLIANCE WITH: 2014 ENERGY CODE SECTION C401.2
 APPLICATION. COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE
 OF THE FOLLOWING:
 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1.
 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND
 C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY
 WITH EITHER SECTION C406.2, C406.3 OR C406.4.
 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2,
 C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE
 BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85
 PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING.
  
 18) SHEET 004_A004 SHOWS 4 EXIT DOORS TO THE EXTERIOR,
 DOORS 1,2,3,& 4. THE DOOR SCHEDULE ON 013_A013 DOES
 INDICATE ON DOORS 2& 4 PANIC HARDWARE BUT NOT ON DOORS
 1 & 3. PLEASE REVIEW FBC-B 1008.1.10 PANIC AND FIRE
 EXIT HARDWARE. DOORS SERVING A GROUP H OCCUPANCY AND
 DOORS SERVING ROOMS OR SPACES WITH AN OCCUPANT LOAD OF
 50 OR MORE IN A GROUP A OCCUPANCY SHALL NOT BE PROVIDED
 WITH A LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR
 FIRE EXIT HARDWARE.
  
 19) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 20) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  