| Plan Review Notes For Permit 16050249 |
| Permit Number |
16050249 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-08-29 06:16:16 | 1) SUBMIT A CONDENSATE RISER FOR REVIEW.SHT. P3.03 HAS | | | BEEN REVISED TO SHOW THE HUB DRAINS, NOT THE CONDENSATE | | | DRAINS AS HAS BEEN REQUESTED 2 PREVIOUS TIMES.SUBMIT A | | | CONDENSATE RISER SHOWING THE SIZE OF THE CONDENSATE | | | DRAINS AND THE EQUIPMENT CAPACITY OF THE DRAINS IN | | | ACCORDANCE WITH 2014 FPC TABLE 314.2.2. | | | 2) WHAT WILL THE SINK IN CONFERENCE ROOM #134 BE USED | | | FOR THAT IT WOULD NOT HAVE TO COMPLY WITH FPC | | | SEC.607.1? | | | 3) THE FAUCETS IN BREAKROOM #110 AND PANTRY #118 SHALL | | | BE EQUIPPED WITH A WATER TEMPERATURE LIMITING DEVICE | | | THAT CONFORMS TO ASSE 1070 AND SHALL LIMIT THE TEMPERED | | | WATER TO A MAXIMUM OF 110 DEGREES FARRENHEIT.THIS WILL | | | ALSO APPLY TO THE CONFERENCE ROOM SINK IF DETERMINED | | | THAT IT NEEDS TEMPERED WATER. | | | 4) PLEASE IDENTIFY THE CONTINUATION LINES ON THE WATER | | | RISER BY IDENTIFICATION TAGS EITHER BY LETTERS OR | | | NUMBERS. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|