| 2016-07-27 11:30:11 | 2ND REVIEW |
| | |
| | |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHOW DIMENSION OF WATER CLOSET OF SIDE WALL. PER FBC |
| | ACC 604.2 LOCATION. |
| | THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| | OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM |
| | TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR |
| | PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17 |
| | INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM |
| | FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY |
| | ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2. |
| | WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR |
| | RIGHT-HAND APPROACH. |
| | |
| | 2. SHOW CLEARANCE AROUND WATER CLOSET TO COMPLY WITH |
| | FBC ACC 604.3.1 SIZE. |
| | CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| | (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| | WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED |
| | PERPENDICULAR FROM THE REAR WALL. |
| | |
| | |
| | 3. PREVIOUS COMMENT 16) SHT. P0.03 - SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS FOR THE OIL GUARD SUMP |
| | PUMP SYSTEM. FPC SEC.1003.4 - EXCEPTION. THE DETAIL YOU |
| | PROVIDED ON P0.03 IS NOT WHAT WE ARE LOOKING FOR. WE |
| | WANT THE SPECIFICATION SHEETS FROM THE SPECIFIC |
| | MANUFACTURE FOR THE PUMP AND OIL GUARD SYSTEM. PER WPB |
| | AMEND. TO FBC 107.2.1 |
| | |
| | 4. PREVIOUS COMMENT 17) SHT.P0.03 - CONDENSATE BOX |
| | DETAIL - HOW WILL THE POSSIBILITY OF WATER SPILLAGE BE |
| | CONTROLLED WITH THIS DEVICE? CLARIFY. THIS DETAIL DOES |
| | NOT SHOW US HOW SPILLAGE WILL BE CONTROLLED. PLEASE |
| | CLARIFY PER WPB AMEND. TO FBC 107.2.1 |
| | |
| | 5. PREVIOUS COMMENT 18) SUBMIT A CONDENSATE RISER FOR |
| | REVIEW. SHOW THE TERMINATION POINT OF THE CONDENSATE |
| | DRAINS. FBC 107.1. YOU RESPONDED THAT A RISER WAS ADDED |
| | BUT COULD NOT FIND IT PLEASE CLARIFY. |
| | |
| | 6. SHT. P0.03 DETAIL FOR WATER HEATER. THE RETURN LINE |
| | OF THE RECIRCULATION SYSTEM SHALL SHOW THAT IT CONNECTS |
| | TO BOTH THE COLD INLET OF THE WATER HEATER AND THE COLD |
| | WATER INLET OF THE THERMOSTATIC MIXING VALVE . PER FBC |
| | PL SEC. 607.2.2 |
| | |
| | 7. SHT. P1.04+P3.03 SNK 1+2 SHALL BE PROVIDE WITH HOT |
| | OR TEMPERED WATER. PER FBC PL 607.1 |
| | |
| | 8. SHT. P3.02 SHOW WATER HAMMER ARRESTOR ON ICE |
| | MACHINE. PER FBC PL 604.9 |
| | |
| | 9. PLEASE SHOW FLOW ARROWS ON HOT WATER RETURN SYSTEM . |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | |