| 2016-07-25 08:08:12 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | GOVERNING CODE: FBC 5TH EDITION (FBC 2014) |
| | |
| | 1. FLORIDA STATUTE 553.71, IT APPEARS THAT THIS |
| | BUILDING MAY QUALIFY AS A THRESHOLD BUILDING; ANY |
| | BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY |
| | CLASSIFICATION AS DEFINED IN THE FLORIDA BUILDING CODE |
| | WHICH EXCEEDS 5,000 SF IN AREA AND AN OCCUPANT CONTENT |
| | OF GREATER THAN 500 PERSONS. |
| | |
| | 2. AS A THRESHOLD BUILDING, THE FOLLOWING IS REQUIRED: |
| | |
| | A. THRESHOLD INSPECTION PLAN; FS 553.79(5)(A), CITY OF |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 109.3.6.1. THE |
| | ENFORCING AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO |
| | PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING |
| | PURSUANT TO A STRUCTURAL INSPECTION PLAN PREPARED BY |
| | THE ENGINEER OR ARCHITECT OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO AND APPROVED BY |
| | THE ENFORCING AGENCY BEFORE THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| | COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| | |
| | B. THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FS |
| | 553.79(5)(A) TO THE MINIMUM INSPECTIONS REQUIRED BY |
| | THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED |
| | TO BE FILED OUT BY ALL PARTIES, NOTARIZED AND RETURNED |
| | TO THIS OFFICE, REVIEWED AND APPROVED PRIOR TO PERMIT |
| | ISSUANCE. CONTACT KEN CONRAD, MANAGER OF THE SPECIAL |
| | INSPECTOR PROGRAM, AT 561-805-6666 FOR ADDITIONAL |
| | INFORMATION. |
| | FORMS WERE SENT TO: [email protected] |
| | ON 5/28/16. |
| | |
| | C. SPECIAL INSPECTOR RESUME': PROVIDE A RESUME' OF |
| | INSPECTION EXPERIENCE ON PREVIOUS PROJECTS FOR REVIEW |
| | BY THE BUILDING OFFICIAL OR HIS DESIGNEE. AFTER THE |
| | RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED. |
| | UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED |
| | FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. THE |
| | RESUME' IS TO BE SUBMITTED TO KEN CONRAD (AND COPY |
| | SAMANTHA HILL), 561-805-6666, [email protected], |
| | [email protected] |
| | |
| | ALL PROSPECTIVE INSPECTORS ARE TO BE APPROVED BY THE |
| | CHIEF BUILDING INSPECTOR AND ALL ARE REQUIRED TO SIGN |
| | THE SPECIAL INSPECTOR AGREEMENT. |
| | |
| | D. CONTRACTOR RESUME': PROVIDE A JOB SUMMARY OR HISTORY |
| | FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO |
| | KEN CONRAD, (PLEASE COPY SAMANTHA HILL) VIA E-MAIL |
| | ([email protected], [email protected]). |
| | |
| | E. PERMIT DOCUMENTS: PAPER SUBMITTALS REQUIRE THREE |
| | SIGNED AND SEALED (IF APPLICABLE) ORIGINAL SETS OF ALL |
| | DOCUMENTS. |
| | |
| | F. THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. |
| | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | MINIMUM BUILDING CODES AND THE APPLICABLE FIRESAFETY |
| | STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS CHAPTER AND CHAPTER 633. |
| | |
| | I WAS UNABLE TO LOCATE THIS STATEMENT ON THE |
| | ARCHITECT'S PLANS. |
| | |
| | THE ENGINEER HAS A SIMILAR STATEMENT BUT LACKS SOME OF |
| | THE STATUTORY LANGUAGE; PLEASE REVISE. |
| | |
| | 3. ADVISORY ONLY; PER FS 553.79, ALL SHORING/RE-SHORE |
| | ENGINEERING IS TO BE REVIEWED BY ENGINEER OF RECORD |
| | AND THREE SIGNED AND SEALED ORIGINAL SETS ARE TO BE |
| | SUBMITTED FOR PLAN REVIEW. THE SHORING/RESHORE |
| | ENGINEERING IS TO BE REVIEWED AND APPROVED PRIOR TO |
| | INSPECTION. THE CITY APPROVED (CITY STAMPED) |
| | SHORING/RE-SHORE ENGINEERING IS TO BE AVAILABLE ON THE |
| | JOB AT THE TIME OF INSPECTION. |
| | |
| | 4. ADVISORY ONLY; PRIOR TO INSTALLATION, A GUARD RAIL |
| | DETAIL IS TO BE SUBMITTED FOR PLAN REVIEW. THIS SHOULD |
| | BE SUBMITTED WITH THE SHORING/RESHORE ENGINEERING. |
| | |
| | 5. SEE IMPACT FEE REVIEW. |
| | |
| | 6. ADVISORY ONLY; SEE ROOF (R STOP) REVIEW. NO ROOFING |
| | INFORMATION PROVIDED IF ROOFING INFORMATION (PRODUCT |
| | APPROVAL REVIEWED BY DESIGNER OF RECORD, ASSEMBLY |
| | PROPOSED, ENHANCED FASTENING CALCULATIONS IF REQUIRED) |
| | IS NOT SUBMITTED PRIOR TO PERMIT ISSUANCE, THIS PERMIT |
| | WILL BE ISSUED WITH PROVISO. ROOF INFORMATION WILL BE |
| | REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED PRIOR |
| | TO INSTALLATION. |
| | |
| | 7, 8. OK |
| | |
| | 9 ? 12. REVISE SHEETS TO ADDRESS COMMENTS 9 THROUGH 12 |
| | FROM REVIEW 1 AS DISCUSSED PER EMAILS AND ATTACHED PDF. |
| | |
| | 13. FBC 107, FS 553.71, SHEET LS101, PROVIDE A TOTAL |
| | OCCUPANT LOAD FOR THE BUILDING, BROKEN DOWN BY FLOOR |
| | AND OCCUPANCY CLASSIFICATION. |
| | |
| | 14. LS101, ROOM 145 SHOWS OCCUPANT LOAD CALCULATED AT |
| | 100 SF PER PERSON. FBC TABLE 1004.1.2, 50 SF GROSS |
| | REQUIRED, PLEASE REVISE. |
| | |
| | 15, 16. OK |
| | |
| | 17. LS101, SOME ROOMS AND SPACES DO NOT INCLUDE AN |
| | OCCUPANT LOAD (137, 138, 139, 140, CORRIDORS, ALL |
| | OTHERS AS APPLICABLE). PLEASE REVISE TO INCLUDE, FBC |
| | 1004. NOTE THAT DEFINITION (CHAPTER 2) OF FLOOR AREA |
| | GROSS INCLUDES ALL AREAS, BUT FLOOR AREA NET EXCLUDES |
| | UNOCCUPIED SPACE. ALTHOUGH THIS IS ASSEMBLY OCCUPANCY, |
| | TABLE 1004.1.2 UTILIZES GROSS SF FOR THE MAJORITY OF |
| | THE SPACES ON THIS FLOOR. PLEASE NOTE THAT THIS |
| | RATIONALE IS SUBSTANTIATED BY THE IBC, BUILDING 2012 |
| | COMMENTARY. |
| | |
| | FBC 107, IT IS ACKNOWLEDGED THAT THE ISSUES OF ROUNDING |
| | AND MISSING OCCUPANT LOAD WILL LIKELY NOT AFFECT THE |
| | LIFE SAFETY DESIGN. HOWEVER, A TOTAL OCCUPANT LOAD IS |
| | REQUIRED FOR INFORMATION REQUIRED TO BE ON THE |
| | CERTIFICATE OF OCCUPANCY. |
| | |
| | 2ND REVIEW, PLEASE REVISE LIFE SAFETY PLAN AND OCCUPANT |
| | LOAD AS DISCUSSED VIA EMAIL. |
| | |
| | 18. BREAK ROOM 110 OCCUPANT LOAD APPEARS TO HAVE A TYPO |
| | (16 SF RATHER THAN 15 SF), ALSO PLEASE ROUND UP, SEE |
| | OTHER COMMENTS, FBC TABLE 1004.1.2. |
| | |
| | 19. LS101, ACADEMICS TEAM ROOM OCCUPANT LOAD IS SHOWN |
| | AS 20 SF PER PERSON, CLARIFY, APPEARS TO BE A TYPO AS |
| | THIS SHOULD BE 15 SF (AND OCC LOAD CALCULATED USING 15 |
| | SF). REVISE PLAN TO CLARIFY USE OF THE SPACE. 15SF IS |
| | FOR AREAS WITH TABLES AND CHAIRS, AREAS WITH CHAIRS |
| | ONLY SHOULD USE 7 SF, AND STANDING AREAS SHOULD USE |
| | 5SF. |
| | |
| | 20. LS101, THE ACADEMICS TEAM ROOM MEANS OF EGRESS |
| | FORCES THE OCCUPANT TO TRAVEL THROUGH A SPACE WHICH IS |
| | A WORK AREA, WHICH APPEARS TO BE PROHIBITED BY FBC |
| | 1014.2. REVISE PLAN TO EITHER MODIFY EXITING STRATEGY |
| | OR REVISE PLAN TO SHOW COMPLIANCE (I.E., SHOW HOW THE |
| | TWO SPACES ARE ACCESSORY TO ONE ANOTHER). |
| | |
| | IF THE RESUBMITTAL PROPOSES TO MAINTAIN EGRESS FROM AN |
| | A2 AREA THROUGH A WORK AREA, PLEASE GET THIS ITEM |
| | REVIEWED PRIOR TO RESUBMITTAL VIA EMAIL. |
| | |
| | 21. LS 101 AND LS 102, NO DIMENSIONS WERE INCLUDED ON |
| | THE PLAN, OR ON THE OTHER A SHEETS. ADD OVERALL |
| | DIMENSIONS. REVISE PLAN TO SHOW COMMON PATH IN ROOM |
| | 145, FBC 1014.3. |
| | |
| | 22. TRAVEL DISTANCE REQUIREMENTS NOTES ARE INCLUDED IN |
| | CODE REVIEW SECTION OF THE LIFE SAFETY PLAN, BUT NO |
| | TRAVEL DISTANCES SHOWN. PLEASE REVISE TO INCLUDE WORST |
| | CASE, FBC 107. |
| | |
| | 23. OK |
| | |
| | 24. LS 101, EXITING STRATEGY VESTIBULE 128 IS NOT |
| | CLEAR, SEE FBC 1005.7.1, REVISE PLAN TO SHOW COMPLIANCE |
| | OR CLARIFY MEANS OF EGRESS PATH. LS101 SHOWS AN ARROW |
| | THROUGH THE VESTIBULE, BUT WHEN BOTH DOORS ARE IN THE |
| | OPEN POSITION, THE CORRIDOR APPEARS TO BE ALMOST |
| | ENTIRELY BLOCKED. |
| | |
| | 25. FBC 1011.1, REVISE PLAN TO INCLUDE ALL REQUIRED |
| | EXIT SIGNS. |
| | |
| | LS101, PLEASE ADD AN EXIT SIGN AT CORRIDOR 164, BETWEEN |
| | ICE AND WET ROOM, OR REVISE EXIT ACCESS. |
| | |
| | 26. 2ND REVIEW, PLEASE REVISE PLAN AS DISCUSSED VIA |
| | EMAIL. |
| | |
| | 26. FBC 1007, REVISE PLAN TO INDICATE METHOD OF |
| | ACCESSIBLE MEANS OF EGRESS SELECTED, REVISE PLAN TO |
| | SHOW COMPLIANCE WITH METHOD SELECTED. |
| | |
| | 27. OK |
| | |
| | 28. ACCESSIBILITY NOT ADDRESSED ON THIS PLAN: |
| | |
| | 206.2.13, EXERCISE MACHINES AND EQUIPMENT |
| | 241, SAUNAS AND STEAM ROOMS |
| | 222, LOCKER ROOMS |
| | 226, DINING SURFACES (TERRACES) |
| | |
| | THESE ITEMS CAN BE ADDRESSED WITH NOTES ON THE PLAN, |
| | SHOP DRAWINGS TO BE SUBMITTED PRIOR TO INSTALLATION. |
| | |
| | 29. AE 112, PROVIDE DIMENSION OF CLEARANCE, 18IN |
| | MINIMUM, PULL SIDE, FOR DOOR A121, FBC 5TH ED |
| | ACCESSIBILITY FIGURE 404.2.4.1(A). |
| | |
| | 30. REVISE PLAN TO SHOW COMPLIANCE WITH FBC 404.6, |
| | ENCLOSURE OF ATRIUMS (FP SHEETS, LS SHEETS). THE NOTE |
| | ON LS SHEETS REFERS TO THE SMOKE PARTITION, BUT I WAS |
| | UNABLE TO LOCATE THE REFERENCE TO WINDOW SPRINKLERS. |
| | |
| | 31. LS101 AND 102, REVISE INTERIOR FINISH NOTES TO |
| | INCLUDE ATRIUM REQUIREMENT, FBC 404.8. |
| | |
| | 32. FBC 107, 703.1, PROVIDE DETAILS (ASSEMBLIES) FOR |
| | THE FIRE RATED ELEMENTS. |
| | |
| | 33. AE801 RATED STUD PARTITION DOES NOT SPECIFY THE UL |
| | NUMBER, PLEASE REVISE TO INCLUDE, FBC 703. |
| | |
| | 34. NOTE CD 01 STATES THIS WAS DESIGNED PER FBC. FBC |
| | TABLE 1604.5, RISK CATEGORY III INCLUDES BUILDINGS OF |
| | ASSEMBLY OCCUPANCY WITH AN OCCUPANT LOAD OVER 300, |
| | SHEET S0.01 INDICATES THIS BUILDING WAS DESIGNED AS |
| | RISK CATEGORY II, PLEASE REVISE. |
| | |
| | 35. PLEASE REVISE FLOOR PLAN TO INCLUDE THE GATE SHOWN |
| | ON DETAIL AE712. IF THIS GATE IS IN THE EXIT DISCHARGE, |
| | REVISE THE DETAIL TO DEPICT THE REQUIRED PANIC |
| | HARDWARE, FBC 1008.2. |
| | |
| | 36. FBC 1008.1.10, REVISE DOOR SCHEDULE AE701 TO |
| | INCLUDE DOOR HARDWARE; IT IS NOT CLEAR WHERE PANIC |
| | HARDWARE IS PROPOSED. |
| | |
| | 37. A SPOT CHECK OF THE ENERGY CALCS WAS DONE; PLEASE |
| | CLARIFY THE FOLLOWING OR REVISE PLAN: |
| | ROOF INSULATION IS R20 ON ENERGY CALCS, R19 ON PLAN |
| | WALL INSULATION IS R3.9 ON ENERGY CALCS, UNABLE TO |
| | LOCATE ON PLAN |
| | WATER HEATER SECTION IS BLANK |
| | EXTERIOR LIGHTING IS BLANK |
| | FLOOR R VALUE 3.73, CLARIFY |
| | |
| | 38. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING |
| | PROVISOS: |
| | |
| | COMPONENTS AND CLADDING PRODUCT APPROVALS REVIEWED BY |
| | DESIGNER OF RECORD ARE TO BE SUBMITTED, REVIEWED AND |
| | APPROVED PRIOR TO INSTALLATION |
| | |
| | SEPARATE PERMITS, PLANS, REVIEWS, AND FEES WILL BE |
| | REQUIRED FOR SIGNS, AWNINGS, PARKING |
| | |
| | |
| | |
| | |