| Plan Review Notes For Permit 16050242 |
| Permit Number |
16050242 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-06-06 16:50:45 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16050242 | | | 6/6/16 | | | | | | 1) INDICATE THE SIZE OF THE RETURN DUCT CONNECTING THE | | | LIVING ROOM GRILL WITH THE AIR HANDLER. | | | | | | 2) IT APPEARS THAT THE TRANSFER GRILL OVER THE NEW | | | BEDROOM DOOR SHOULD INDICATE 150 CFM'S RATHER THAN 100 | | | CFM'S BASED ON THE AMOUNT OF SUPPLY CFM'S ENTERING THE | | | ROOM. IT APPEARS THAT THIS TRANSFER AIR IS TO THEN BE | | | CONVEYED TO THE LIVING ROOM RETURN GRILL?- PLEASE | | | CLARIFY. | | | | | | 3) INDICATE THE CAPACITY OF THE EXISTING AC SYSTEM | | | (COOLING AND HEATING BTUH, AND SUPPLY CFMS) AND | | | INDICATE HOW THE SUPPLY AIR TO THE NEW ROOM LAYOUTS WAS | | | DETERMINED OR SIZED. IT APPEARS THAT THE CFM TOTALS FOR | | | THE LIVING ROOM AND KITCHEN MAY BE INADEQUATE PER SF. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|