| Plan Review Notes For Permit 16050242 |
| Permit Number |
16050242 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-11 08:39:36 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16050242 | | | 5/11/16 | | | | | | 1) PROVIDE THE PROJECT ADDRESS ON THE PERMIT | | | APPLICATION. PLEASE NOTE A SUB-PERMIT FOR THE AC WORK | | | MUST BE SUBMITTED. | | | 2) REFER TO SECTION 601.5 FBC-14 MECHANICAL AND | | | INDICATE HOW MANY CFM'S OF AIR IS TO BE TRANSFERRED | | | THROUGH THE 10X16 GRILL, AND CLARIFY HOW THAT AIR, AND | | | THE SUPPLY AIR INTO THE BEDROOM WILL BE RETURNED TO THE | | | AIR HANDLER. | | | 3) THE 6X8 DUCT IS UNDERSIZED FOR 300 CFM'S OF SUPPLY | | | AIR PER ASHRAE STANDARD DUCT SIZING. | | | 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW | | | RANGE AND HOOD. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|