Plan Review Notes
Plan Review Notes For Permit 16050242
Permit Number 16050242
Review Stop M
Sequence Number 1
Notes
Date Text
2016-05-11 08:39:361ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16050242
 5/11/16
  
 1) PROVIDE THE PROJECT ADDRESS ON THE PERMIT
 APPLICATION. PLEASE NOTE A SUB-PERMIT FOR THE AC WORK
 MUST BE SUBMITTED.
 2) REFER TO SECTION 601.5 FBC-14 MECHANICAL AND
 INDICATE HOW MANY CFM'S OF AIR IS TO BE TRANSFERRED
 THROUGH THE 10X16 GRILL, AND CLARIFY HOW THAT AIR, AND
 THE SUPPLY AIR INTO THE BEDROOM WILL BE RETURNED TO THE
 AIR HANDLER.
 3) THE 6X8 DUCT IS UNDERSIZED FOR 300 CFM'S OF SUPPLY
 AIR PER ASHRAE STANDARD DUCT SIZING.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW
 RANGE AND HOOD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  