2016-06-02 15:03:092ND REVIEW: FBC 2014 MECHANICAL, EXISTING
 PERMIT #16050233
 5/11/2016
  
 COMMENTS #1, & 2B FROM THE 1ST REVIEW STILL EXIST. I
 HAVE RE-PRINTED THEM BELOW. PLEASE REVIEW AND REVISE
 THE PLAN ACCORDINGLY.
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING, AND
 PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 PROPOSED OCCUPANCY IN COMPLIANCE WITH TABLE 403.3
 FBC-14 MECHANICAL.
 2 B) PROVIDE THE SUPPLY AND RETURN CFM'S AT EACH
 DIFFUSER AND GRILL.
 3) RETURN AIR FROM THE EQUIPMENT CLOSET IS PROHIBITED
 PER SECTION 918.6 MECHANICAL.
  