| Plan Review Notes For Permit 16050233 |
| Permit Number |
16050233 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-06-02 15:03:09 | 2ND REVIEW: FBC 2014 MECHANICAL, EXISTING | | | PERMIT #16050233 | | | 5/11/2016 | | | | | | COMMENTS #1, & 2B FROM THE 1ST REVIEW STILL EXIST. I | | | HAVE RE-PRINTED THEM BELOW. PLEASE REVIEW AND REVISE | | | THE PLAN ACCORDINGLY. | | | | | | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING, AND | | | PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE | | | PROPOSED OCCUPANCY IN COMPLIANCE WITH TABLE 403.3 | | | FBC-14 MECHANICAL. | | | 2 B) PROVIDE THE SUPPLY AND RETURN CFM'S AT EACH | | | DIFFUSER AND GRILL. | | | 3) RETURN AIR FROM THE EQUIPMENT CLOSET IS PROHIBITED | | | PER SECTION 918.6 MECHANICAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|