| Plan Review Notes For Permit 16050233 |
| Permit Number |
16050233 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-06-15 08:49:31 | 2ND REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | - PLEASE PROVIDE X-RAY EQUIPMENT MANUFACTURE | | | SPECIFICATION CUT SHEETS ( 2ND REQUEST ) | | | | | | - LOAD CALCS AND PANEL SCHEDULE REFLECT SINGLE PHASE | | | VOLTAGE AND RISER DIAGRAM SHOWS THREE PHASE ? PLEASE | | | CLARIFY AND MATCH INFORMATION. ( 2ND REQUEST ) |
|