| Plan Review Notes For Permit 16050233 |
| Permit Number |
16050233 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-11 11:55:06 | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1.DRAIN NOT SHOWN FOR EXAM ROOM 3 PLEASE CLARIFY . PER | | | WPB AMEND TO FBC SEC. 107.2.1 | | | | | | 2.DRAIN NOT SHOWN FOR BREAKROOM /FUTURE EXAM PLEASE | | | CLARIFY. PER WPB AMEND TO FBC SEC. 107.2.1 | | | | | | 3. A VENT IS REQUIRED ON 2IN DRAIN FOR EXAM CHAIRS. PER | | | FBC PL SEC. 901.2.1 | | | | | | 4. PROVIDE A RISER DIAGRAM FOR THE WATER, VACUUM AND | | | COMPRESSED AIR SYSTEMS. PER WPB AMEND. TO FBC SEC. | | | 107.3.5.1.3(13) | | | | | | 5.SHOW VACUUM AND COMPRESSED AIR ON PLAN VIEW. PER WPB | | | AMEND TO FBC SEC. 107.2.1 | | | | | | 6. PROVIDE MANUFACTURE SPECS ON ALL EQUIPMENT. PER WPB | | | AMEND TO FBC SEC. 107.2.1 | | | | | | 7. SHOW VENTING FOR VACUUM SYSTEM. SHALL COMPLY WITH | | | FBC PL 713.6 | | | | | | 8. BACK FLOW DEVICE REQUIRED FOR EXAM CHAIR WATER | | | CONNECTION. PER FBC PL SEC. 608.3.1 | | | | | | 9. IF THE VACUUM SYSTEM REQUIRES A DRAIN INCLUDE IT ON | | | THE PLAN VIEW AND SANITARY RISER. PER WPB AMEND TO FBC | | | SEC. 107.2.1 | | | |
|