2016-05-11 11:55:061ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1.DRAIN NOT SHOWN FOR EXAM ROOM 3 PLEASE CLARIFY . PER
 WPB AMEND TO FBC SEC. 107.2.1
  
 2.DRAIN NOT SHOWN FOR BREAKROOM /FUTURE EXAM PLEASE
 CLARIFY. PER WPB AMEND TO FBC SEC. 107.2.1
  
 3. A VENT IS REQUIRED ON 2IN DRAIN FOR EXAM CHAIRS. PER
 FBC PL SEC. 901.2.1
  
 4. PROVIDE A RISER DIAGRAM FOR THE WATER, VACUUM AND
 COMPRESSED AIR SYSTEMS. PER WPB AMEND. TO FBC SEC.
 107.3.5.1.3(13)
  
 5.SHOW VACUUM AND COMPRESSED AIR ON PLAN VIEW. PER WPB
 AMEND TO FBC SEC. 107.2.1
  
 6. PROVIDE MANUFACTURE SPECS ON ALL EQUIPMENT. PER WPB
 AMEND TO FBC SEC. 107.2.1
  
 7. SHOW VENTING FOR VACUUM SYSTEM. SHALL COMPLY WITH
 FBC PL 713.6
  
 8. BACK FLOW DEVICE REQUIRED FOR EXAM CHAIR WATER
 CONNECTION. PER FBC PL SEC. 608.3.1
  
 9. IF THE VACUUM SYSTEM REQUIRES A DRAIN INCLUDE IT ON
 THE PLAN VIEW AND SANITARY RISER. PER WPB AMEND TO FBC
 SEC. 107.2.1
  