| Plan Review Notes For Permit 16050233 |
| Permit Number |
16050233 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-11 10:17:03 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16050233 | | | 5/11/2016 | | | | | | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING, AND | | | PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE | | | PROPOSED OCCUPANCY IN COMPLIANCE WITH TABLE 403.3 | | | FBC-14 MECHANICAL. | | | 2) SHEET MEP-2: THE HVAC PLAN IS INCOMPLETE: A) LABEL | | | ALL DIFFUSERS AND RETURN GRILLS AS EITHER NEW (N), | | | EXISTING (E), OR RELOCATED (R). B) PROVIDE THE SUPPLY | | | AND RETURN CFM'S AT EACH DIFFUSER AND GRILL. C) SHOW | | | NEW DUCT INSTALLATIONS OR RELOCATIONS. | | | 3) PROVIDE AN AIR DEVICE SCHEDULE. | | | 4) PROVIDE DUCT HANGING AND CONNECTION DETAILS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|