Plan Review Notes
Plan Review Notes For Permit 16050233
Permit Number 16050233
Review Stop M
Sequence Number 1
Notes
Date Text
2016-05-11 10:17:031ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16050233
 5/11/2016
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING, AND
 PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 PROPOSED OCCUPANCY IN COMPLIANCE WITH TABLE 403.3
 FBC-14 MECHANICAL.
 2) SHEET MEP-2: THE HVAC PLAN IS INCOMPLETE: A) LABEL
 ALL DIFFUSERS AND RETURN GRILLS AS EITHER NEW (N),
 EXISTING (E), OR RELOCATED (R). B) PROVIDE THE SUPPLY
 AND RETURN CFM'S AT EACH DIFFUSER AND GRILL. C) SHOW
 NEW DUCT INSTALLATIONS OR RELOCATIONS.
 3) PROVIDE AN AIR DEVICE SCHEDULE.
 4) PROVIDE DUCT HANGING AND CONNECTION DETAILS.
  