| 2016-05-12 12:55:24 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. PLEASE PROVIDE A GENERAL NOTE TO INDICATE NEC 517.13 | | | SEE VERBIAGE IN CODE FOR REDUNDANT GROUNDING AND PART V | | | OF THE NEC 517 REGARDING X-RAY EQUIPMENT. | | | 2. PROVIDE SPECS OF X-RAY EQUIPMENT BEING INSTALLED. | | | FBC 107.3.5 | | | 3. CLARIFY IF THE VOLTAGE TO TENANT IS SINGLE PHASE OR | | | 3 PHASE. SEE PANEL SCHEDULE SHOWS SINGLE PHASE BUT | | | VACUUM PUMP AND AIR COMP. EQUIPMENT IS SHOWN ON A | | | SINGLE BREAKER 230VOLTS. PLEASE CORRECT TO SHOW | | | ADEQUATE LOADS AND VOLTAGES. FBC 107.3.5 | | | 4. ALL RECEPTACLES WITHIN 6FT OF SINKS TO HAVE GFCI | | | PROTECTION, LABEL FLOOR PLANS SEE WORK AREA AND DENTAL | | | CHAIRS. NEC 210.8B7 | | | 5. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. PLEASE | | | FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS | | | REGARDING THIS PROJECT. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|