| Plan Review Notes For Permit 16050202 |
| Permit Number |
16050202 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-25 13:49:54 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. JOHN HOLT, PE DOES NOT HAVE A CURRENT ENGINEERING | | | LICENSE, FS 471. WWW.MYFLORIDALICENSE.COM. ENGINEERING | | | REQUIRED FOR COMMERCIAL PROJECTS, FBC 1609, FS 471. | | | | | | 2. THE STRUCTURAL SPECIFICATION FOR SIGN FASTENING IS | | | NOT CLEAR. THE TALLEST LETTER IS OVER 2'. THE | | | STRUCTURAL SPECIFICATION STATES "AVG (3) PER LETTER" | | | (REFERRING TO TAP CONS). THE LETTER "H" IS OVER 2' | | | TALL, HAS TWO SECTIONS. IT IS NOT CLEAR HOW THREE | | | FASTENERS WILL BE ADEQUATE. PROVIDE CALCULATIONS. | | | | | | 3. TAP CON, 3/16" X 1 3/4" WAS SPECIFIED AS THE | | | FASTENER TO BE USED. ISN'T THAT A BRAND? DOESN'T THAT | | | COMPANY MAKE MANY DIFFERENT ANCHORS, ALL WITH DIFFERENT | | | VALUES? THE SUBSTRATE WAS NOT SPECIFIED; REVISE PLAN SO | | | TO INCLUDE THIS INFORMATION? REVISE PLAN TO MORE | | | CLEARLY SPECIFY THE ANCHOR WHICH THE ENGINEER INTENDS | | | TO BE USED. | | | | | | 4. THE SEAL ON THE PLAN IS NOT ENTIRELY LEGIBLE. FS471, | | | FAC61G15-23.002 REQUIRES A LEGIBLE SEAL. ALL TEXT IS | | | DIFFICULT TO READ, IN PARTICULAR THE LICENSE NUMBER. | | | | | | 5. FBC 109, PROVIDE A VERIFIABLE COPY OF THE CONTRACT | | | FOR THIS JOB. | | | | | | | | | |
|