| 2016-05-10 07:02:41 | 1) THIS PERMIT APPLICATION IS FOR THE INSTALLATION OF |
| | GAS PIPING TO A WATER HEATER, DRYER AND RANGE YET A GAS |
| | PLAN HAS NOT BEEN SUBMITTED, ONLY AN ELECTRICAL PLAN |
| | SHOWING THESE APPLIANCES AS ELECTRIC.. SUBMIT TWO |
| | COPIES OF A GAS PLAN THAT CLEARLY REFLECTS THE ENTIRE |
| | SCOPE OF WORK TO BE DONE. FBC 107.2.1. |
| | 2) THE FOLLOWING INFORMATION, AT A MINIMUM, SHALL BE |
| | SUBMITTED FOR REVIEW: |
| | |
| | GAS PERMIT APPLICATION REQUIREMENTS |
| | 3. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL |
| | GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC. |
| | G2413. |
| | |
| | 4. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS STEEL TUBING |
| | (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO |
| | FBC SEC.107.2.1. |
| | |
| | 5. TYPE OF GAS (LP OR NATURAL). |
| | |
| | 6 BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON |
| | THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS SECS.401.8 |
| | THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37) OR |
| | 2014 FBC-RES. SEC. G2413. |
| | |
| | 7. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (METER |
| | OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE |
| | BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS |
| | SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3. |
| | |
| | 8. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR ALL |
| | APPLIANCES PER THE 2014 FBC-FUEL GAS CODE SEC.304.1 OR |
| | 2014 FBC-RES. SEC. G 2407. |
| | |
| | 9. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES. |
| | SEC. G2413.2. . |
| | |
| | 10. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE |
| | AND TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS |
| | SECS. 502 THRU 505 OR 2014 FBC-RES. SEC.G2426. |
| | |
| | 12. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. |
| | |
| | 13. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP |
| | TANK(S), TYPE OF TANK ( DOT OR ASME ), THE DISTANCE OF |
| | THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT |
| | PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL |
| | SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND |
| | THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF |
| | VALVE OF THE TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | 14 CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS ABOVE |
| | GROUND OR BELOW GROUND, AND SHOW THE METHOD OF REQUIRED |
| | PROTECTION FOR THE LP TANK AND APPURTENANCES PER NFPA |
| | 58. IF THE TANK IS BELOW GROUND IT SHALL BE ANCHORED |
| | PER NFPA 58 SEC.3-2.2.7 (H). IF ABOVE GROUND, THE TANK |
| | SHALL BE SECURELY ANCHORED TO WITHSTAND 170 MPH ULT |
| | WIND LOAD PER THE FLORIDA BUILDING CODE. |
| | |
| | 15. SHOW THE LOCATION OF ALL MEDIUM PRESSURE REGULATORS |
| | ( IF APPLICABLE ). A LISTED SHUTOFF VALVE SHALL BE |
| | INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR PER |
| | 2014 FGC SEC.409.4. |
| | |
| | 17) SEDIMENT TRAPS SHALL BE INSTALLED IN ACCORDANCE |
| | WITH THE 2014 FGC SEC.408.4. |
| | |
| | 18) SUBMIT TWO COPIES OF THE APPROPRIATE SIZING TABLE |
| | FROM THE 2014 FUEL GAS CODE FOR THE SIZING OF THIS |
| | SYSTEM. FBC 107.2.1. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |