| 2016-05-11 16:46:56 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16050165 | | | 5/11/16 | | | | | | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW | | | 3-TON RTU- SECTION C403.2.1 FBC-14 ENERGY CONSERVATION. | | | 2) PROVIDE EXHAUST VENTILATION FOR THE KITCHENETTE- | | | TABLE 6-4 ASHRAE 62.1-2010. | | | 3) PROVIDE A MECHANICAL ROOF PLAN SHOWING LOCATION OF | | | THE NEW RTU AND THE CONDENSATE PIPE DISPOSAL RUN AND | | | DISCHARGE LOCATION. | | | 4) PROVIDE SHUTOFF DAMPER CONTROLS FOR THE O/A- SECTION | | | C403.2.4.4 FBC-14 ENERGY. | | | 5) THE RTU ANCHORING DETAIL IS INCOMPLETE: A) PROVIDE | | | COMPLETE WIND LOAD DESIGN CRITERIA- INCLUDING THE | | | EXPOSURE CATEGORY AND HEIGHT ADJUSTMENT COEFFICIENT, | | | AND DESIGN PRESSURES. B) INDICATE HOW THE CURB WILL BE | | | ATTACHED TO THE ROOF STRUCTURE | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|