| Plan Review Notes For Permit 16050132 |
| Permit Number |
16050132 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-25 15:32:33 | 1501 NORTHPOINT PARKWAY SUITE #104 | | | PERMIT #16050132 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PLANS ARE NOT TO SCALE. | | | | | | SEVERAL ROOMS DO NOT INDICATE A NAME/FUNTION. | | | | | | NO CEILING HEIGHTS INDICATED FOR CEILING MOUNTED | | | APPLIANCES. | | | | | | NOTE #23 INDICATES THIS IS A STORAGE OCCUPANCY; | | | HOWEVER, MORE THAN HALF OF THE SUITE IS BUSINESS | | | OCCUPANCY WITH AN ASSUMED AMBIENT NOISE OF 55DB. | | | PROVIDING AN ASSUMED SOUND LEVEL OF 58DB WILL NOT BE | | | SUFFICIENT. | | | | | | INSUFFICIENT NOTIFICATION DEVICES IN SEVERAL OFFICE | | | AREAS. | | | | | | PLANS DO NOT SHOW ANY DUCT SMOKE DETECTORS. CONFIRM | | | HVAC UNITS ARE NOT SUPPLYING MORE THAN 2,000 CFM. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|