| Plan Review Notes For Permit 16050108 |
| Permit Number |
16050108 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-01 17:34:35 | FLORIDA ENERGY CODE | | | FORM R405-2014 IS NOT SIGNED OR DATED. PROVIDE | | | SIGNATURE OF OWNER/AGENT. | | | | | | AS PER THE TRANE DUCTULATOR THE MASTER BATHROOM AND | | | COOPER'S BATHROOM EXHAUST DUCT MUST BE 6" FOR 100 CFM. | | | | | | AHU #2 AND AHU #3 SUPPLY AIR THROUGH THE OUTLETS ON THE | | | PLANS EXCEED EACH SPECIFIC AHU MAXIMUM AMOUNT OF CFM ON | | | EQUIPMENT SCHEDULE. CHECK CFM QUANTITIES AND MAKE | | | CORRECTIONS. | | | | | | M1503.4 MAKEUP AIR REQUIRED. | | | EXHAUST HOOD SYSTEMS CAPABLE OF EXHAUSTING IN EXCESS OF | | | 400 CUBIC FEET PER MINUTE (0.19 M3/S) SHALL BE PROVIDED | | | WITH MAKEUP AIR AT A RATE APPROXIMATELY EQUAL TO THE | | | EXHAUST AIR RATE. SUCH MAKEUP AIR SYSTEMS SHALL BE | | | EQUIPPED WITH A MEANS OF CLOSURE AND SHALL BE | | | AUTOMATICALLY CONTROLLED TO START AND OPERATE | | | SIMULTANEOUSLY WITH THE EXHAUST SYSTEM. | | | |
|