Plan Review Notes
Plan Review Notes For Permit 16050108
Permit Number 16050108
Review Stop M
Sequence Number 1
Notes
Date Text
2016-06-01 17:34:35FLORIDA ENERGY CODE
 FORM R405-2014 IS NOT SIGNED OR DATED. PROVIDE
 SIGNATURE OF OWNER/AGENT.
  
 AS PER THE TRANE DUCTULATOR THE MASTER BATHROOM AND
 COOPER'S BATHROOM EXHAUST DUCT MUST BE 6" FOR 100 CFM.
  
 AHU #2 AND AHU #3 SUPPLY AIR THROUGH THE OUTLETS ON THE
 PLANS EXCEED EACH SPECIFIC AHU MAXIMUM AMOUNT OF CFM ON
 EQUIPMENT SCHEDULE. CHECK CFM QUANTITIES AND MAKE
 CORRECTIONS.
  
 M1503.4 MAKEUP AIR REQUIRED.
 EXHAUST HOOD SYSTEMS CAPABLE OF EXHAUSTING IN EXCESS OF
 400 CUBIC FEET PER MINUTE (0.19 M3/S) SHALL BE PROVIDED
 WITH MAKEUP AIR AT A RATE APPROXIMATELY EQUAL TO THE
 EXHAUST AIR RATE. SUCH MAKEUP AIR SYSTEMS SHALL BE
 EQUIPPED WITH A MEANS OF CLOSURE AND SHALL BE
 AUTOMATICALLY CONTROLLED TO START AND OPERATE
 SIMULTANEOUSLY WITH THE EXHAUST SYSTEM.
  