| Plan Review Notes For Permit 16050068 |
| Permit Number |
16050068 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-04 16:35:53 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) SHEET T11 F01 - THERE APPEARS TO DISCREPANCIES IN | | | THE DEVICE COUNTS AND CALCULATIONS. | | | | | | 2) SHEET T11 F01 - THERE ARE 11 SMOKE DETECTORS | | | INDICATED IN THE DIAGRAM; HOWEVER, 12 ARE INDICATED ON | | | THE FLOOR PLAN. | | | | | | 3) SHEET T11 F01 - THERE ARE 9 STROBES INDICATED ON THE | | | DIAGRAM AND FLOOR PLANS; HOWEVER, 10 ARE INDICATED IN | | | THE CALCULATIONS. | | | | | | 4) SHEET T11 F01 - THE DEVICE TABLES INDICATES 4 WALL | | | HORN STROBES; HOWEVER, CEILING MOUNTED HORN STROBES ARE | | | INDICATED ON THE FLOOR PLAN. | | | | | | 5) SHEET T11 F01 - 4 HORN STROBES ARE INDICATED ON THE | | | FLOOR PLAN AND DEVICE TABLE; HOWEVER, 3 HORN STROBES | | | ARE INDICATED IN THE VOLTAGE DROP CALCULATIONS. | | | | | | PLEASE REVIEW AND PROVIDE ADJUSTMENTS OR CLARIFICATIONS | | | WHERE APPLICANLE. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|