2016-05-05 13:24:38JOB PERMIT NUMBER:16050038
 JOB ADDRESS: 2100 45TH STREET
 WEST PALM BEACH FLORIDA 33407
 DATE: MAY 5 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 - FBC-E C405.7.3 VOLTAGE DROP. FEEDERS & CUSTOMER OWNED
 SERVICE CONDUCTORS SHALL BE SIZED FOR A MAXIMUM OF 2%
 VOLTAGE DROP. BRANCH CIRCUITS SHALL BE SIZED FOR A
 MAXIMUM OF 3% VOLTAGE DROP. PLEASE REFERENCE THIS CODE
 OR PROVIDE WIRE SIZE IN ACCORDANCE WITH LOAD DEMANDS TO
 VERIFY IF VOLTAGE DROP WAS TAKEN INTO CONSIDERATION.
 - FBC-E C405.2.4 EXTERIOR LIGHTING CONTROLS. LIGHTING
 NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND
 A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS..
 - PROVIDE A DEMAND CALCULATION SUMMARY OF LOAD BEING
 ADDED AND A PANEL SCHEDULE SHOWING WIRE / CONDUCTOR /
 BREAKER SIZES WITH CIRCUITS BEING IDENTIFIED ON SITE
 FLOOR PLAN. WPBA 107
 - MUST COMPLY WITH WIND LOAD RATING MINIMUM
 REQUIREMENTS FOR POLE LIGHTS. ( BUILDING PLAN EXAMINER
 TO VERIFY ) FBC CHAPTER 16
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  