| Plan Review Notes For Permit 16050027 |
| Permit Number |
16050027 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-13 12:00:59 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA RES BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. A PANEL BOARD MUST BE AT THE NEW DETACHED STRUCTURE | | | AND A GROUNDING ELECTRODE CONDUCTOR MUST BE SHOWN PER | | | E3607.3. SHOW PANEL LOCATION ON FLOOR PLAN OF DETACHED. | | | 2. PLEASE SHOW THE FEEDER CONDUCTOR SIZES AND EQUIPMENT | | | GROUNDING CONDUCTOR REQUIRED WITH THESE FEEDERS. FBC | | | 107.3.5 | | | 3. SHOW ONE LINE REFLECTING SERVICE AND DETACHED BEING | | | FED PER COMMENT ABOVE. FBC 107.3.5 | | | 4. PROVIDE GENERAL NOTES TO INDICATE REQUIREMENTS FOR | | | AFCI PROTECTION, TAMPER RESISTANT RECEPTACLES. FBC RES | | | E3902 E4002.14 | | | 5. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | | QUESTIONS OR CONCERNS. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|