| Date |
Text |
| 2016-05-09 12:50:45 | 1ST REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #16050024 |
| | 5/9/16 |
| | |
| | 1) THE SUBMITTED PLANS FOR THE NEW SURGICAL CENTER DO |
| | NOT REFLECT APPLICABLE AND COMPLIANT CODE DESIGN, AND |
| | MUST BE REVISED TO PROVIDE ENOUGH INFORMATION FOR A |
| | COMPLETE MECHANICAL REVIEW. |
| | A) REFER TO SECTION 451 AMBULATORY SURGICAL CENTERS |
| | FBC-14 BUILDING AND PROVIDE DOCUMENTATION OF PLAN |
| | APPROVAL FROM AHCA- SECTION 451.1.5. |
| | B) IN ADDITION TO THE LIST OF APPLICABLE CODES ON SHEET |
| | CVR, THE PLANS SHALL ALSO BE DESIGNED IN ACCORDANCE |
| | WITH- SECTION 451.2.1: THE FIRE CODES DESCRIBED IN |
| | CHAPTER 69A-3.012, STANDARDS OF THE NATIONAL FIRE |
| | PROTECTION ASSOCIATION ADOPTED, FLORIDA ADMINISTRATIVE |
| | CODE & SECTION AND 451.2.2: GUIDELINES FOR DESIGN AND |
| | CONSTRUCTION OF HEALTH CARE FACILITIES AND ASHRAE |
| | 170-2008. |
| | 2) THE PLANS APPEAR TO INDICATE AN "OUTPATIENT" |
| | SURGICAL FACILITY. PLEASE REFER TO SECTION 3.1-8.2.1.1 |
| | GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH CARE |
| | FACILTIES. REVIEW ALL SUB-SECTIONS AND ASHRAE 170-2008 |
| | (PART 6 OF THE GUIDELINES) AND RE-DESIGN THE HVAC |
| | SYSTEMS ACCORDINGLY. PLEASE SEE TABLE 7-1 DESIGN |
| | PARAMETERS ASHRAE 170 FOR VENTILATION REQUIREMENTS. |
| | PROVIDE A VENTILATION TABLE ON THE PLAN FOR ALL ROOMS |
| | AND SPACES IN ACCORDANCRE WITH THE TABLE. |
| | 3) THE CURRENT PLAN SHOWS A TRANSFER GRILL AT THE |
| | JANITOR/CORRIDOR, HOWEVER CORRIDORS SHALL NOT SERVE AS |
| | RETURN AIR DUCTS- SECTION 601.2 FBC-14 MECHANICAL. |
| | PLEASE CORRECT THE PLAN |
| | 4) PLEASE INDICATE WHICH THE FRICTION RATE USED TO SIZE |
| | THE NEW SUPPLY AND RETURN DUCTS- THE MAIN DUCT TRUNKS |
| | APPEAR UNDERSIZED. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |