| Permit Number |
16050022 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-04-26 11:49:41 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC | | | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE | | | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER | | | OF RECORD. THE PRODUCT APPROVALS ARE REQUIRED TO BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD. | | | | | | 2) ON THE ENERGY FORM R405-2014, THE NUMBERS FOR THE | | | COOLING BTUS AND THE SEER ARE SWITCHED. THE SEER SHOULD | | | BE 16 AND THE BTUS SHOULD BE 18,000. FBC 107.2.1 | | | | | | 3) THE AHRI CERTIFICATION LETTER DOES NOT MATCH THE | | | MODELS SPECIFIED ON THE PLANS. FBC 107.2.1 |
|