| 2016-09-06 18:58:28 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SUBMIT TWO SETS OF ENERGY CODE COMPLIANCE FORMS THAT |
| | HAVE THE SIGNATURES OF THE PREPARER AND THE |
| | OWNER/AGENT. FBC ENERGY CONSERVATION R103 - COMPLETED |
| | FORMS R402 OR R405 ARE ACCEPTABLE. |
| | |
| | 2) PROVIDE SIGNED AND SEALED CALCULATIONS TO VERIFY |
| | THAT THE (2) 2 X 12 BEAM SPANNING 15 FEET CAN SUPPORT |
| | THE 40 PSF LIVE LOAD AND DEAD LOAD OF THE BALCONY. FBC |
| | 107.2.1.3 |
| | |
| | 3) THE PLANS DO NOT SPECIFY ANY CROSS BRACING OF THE |
| | DECK OR THE 4 X 4 POSTS THAT ARE SUPPORTING THE DECK. |
| | PROVIDE SIGNED AND SEALED CALCULATIONS TO SHOW THAT THE |
| | 4" X 4" X 8' WOOD POSTS ARE CAPABLE OF RESISTING THE |
| | LATERAL LOADS, WIND LOADS, ETC. |
| | |
| | 4) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT |
| | APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION |
| | INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE RIDGE |
| | OR ROOF VENT, THE SIDING (IF IT IS ALUMINUM OR VINYL) |
| | AND THE ALUMINUM SOFFIT MATERIAL. |
| | |
| | 5) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE |
| | SINGLE OUTSWING DOOR HAS A MAXIMUM NEGATIVE DESIGN |
| | PRESSURE FOR THE DOOR OF (-50 PSF) IS NOT ADEQUATE FOR |
| | THE DOOR LOCATED ON THE FIRST FLOOR IN THE END ZONE, |
| | WHICH REQUIRES -54.8 PSF. SUBMIT CORRECT PRODUCT |
| | APPROVALS. FBC-R301.2.1 |
| | |
| | 6) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE |
| | SECTIONAL GARAGE DOOR HAS MAXIMUM DESIGN PRESSURES OF |
| | +36, -42.5 PSF WHICH ARE NOT ADEQUATE. THE PLANS |
| | SPECIFY THAT THE REQUIRED PRESSURES ARE +37.5, -42.5 |
| | PSF. SUBMIT CORRECT PRODUCT APPROVALS. FBC-R301.2.1 |
| | |
| | 7) SUBMIT TWO COPIES OF THE PRODUCT EVALUATION REPORTS |
| | WITH INSTALLATION REQUIREMENTS FOR THE OPEN CELL SPRAY |
| | FOAM INSULATION THAT IS SPECIFIED ON THE PLANS. FBC |
| | R316 |
| | |
| | 8) THE SECOND FLOOR OF THIS STRUCTURE IS CONDITIONED |
| | SPACE. THE FLOOR/CEILING ASSEMBLY ABOVE THE GARAGE IS |
| | REQUIRED TO HAVE THERMAL INSULATION. FBC ENERGY |
| | CONSERVATION R402.1 |
| | |
| | 9) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A |
| | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |