Plan Review Notes
Plan Review Notes For Permit 16041276
Permit Number 16041276
Review Stop P
Sequence Number 3
Notes
Date Text
2016-08-17 11:57:041) TOILET PAPER DISPENSERS SHALL BE LOCATED 7-9 INCHES
 FROM THE FRONT OF THE WATER CLOSET TO THE CENTER LINE
 OF THE DISPENSERS. FAC SEC. 604.9.6.
 2) THE HEIGHT OF THE GRAB BARS SHALL BE MEASURED FROM
 FINISH FLOOR TO THE TOP OF THE GRIPPING SURFACE, NOT TO
 THE CENTERLINE AS SHOWN ON THE PLANS. FAC SEC. 609.4.
 3) THE SHOWER SEAT SHALL BE LOCATED A MAXIMUM OF 19
 INCHES ABOVE THE FINISH FLOOR, NOT TWENTY INCHES AS
 SHOWN. FAC SEC.610.3.
 5) THE BREAKROOM SINK SHALL BE LOCATED A MAXIMUM OF 34
 INCHES ABOVE FINISH FLOOR.FAC SEC. 606.3.
 6) THE HEIGHT OF THE FEMININE PRODUCT DISPENSER SHALL
 COMPLY WITH FAC SEC. 308. MAXIMUM OF 48 INCHES ABOVE
 FINISH FLOOR.
 7) THE LOCATION OF THE SHOWER CCONTROLS IN THE
 HANDICAPPED ACCESSIBLE SHOWER SHALL COMPLY WITH FAC
 SEC. 608.5.3.
 8) PLEASE CORRECT THE ADA NOTES ON SHT. A4.10 TO COMPLY
 WITH FAC. SEE NOTE #5, 7, &10.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW