2016-06-27 12:46:522ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16041276
 6/27/16
  
 1) THE VOIDED PLAN SHEETS MUST BE REMOVED FROM THE
 RESUBMITTED PLAN SETS- SECTION 107.2.1.4 WPB AMENDMENTS
 TO THE FBC:
  
 QUALITY OF BUILDING PLANS. BUILDING PLANS SHALL BE
 DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL
 PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER
 TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE
 WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
  
 2) THE STRUCTURAL PLANS EXAMINER HAS DETERMINED THE
 OCCUPANT LOADS FOR THE MULTI-USE AREAS TO BE GREATER
 THAN THE LOADS USED IN THE VENTILATION CALULATION ON
 SHEET M1.1. IF THE ENGINEER IS CHOOSING TO USE THE
 EXCEPTION UNDER SECTION 403.3, AS HE IS STATING IN THE
 RESPONSE NARRATIVE, THEN SUFFICIENT DOCUMENTATION MUST
 BE SUBMITTED TO JUSTIFY THE REDUCED OCCUPANT LOAD AND
 O/A REQUIERMENT- SEE SECTION 403.3 EXCEPTION.
  
 3) REFER TO SECTION 504.5 AND PROVIDE A MEANS OF MAKEUP
 AIR FOR THE DRYER IN THE CLOSET.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  