| 2016-06-27 12:46:52 | 2ND REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #16041276 |
| | 6/27/16 |
| | |
| | 1) THE VOIDED PLAN SHEETS MUST BE REMOVED FROM THE |
| | RESUBMITTED PLAN SETS- SECTION 107.2.1.4 WPB AMENDMENTS |
| | TO THE FBC: |
| | |
| | QUALITY OF BUILDING PLANS. BUILDING PLANS SHALL BE |
| | DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL |
| | PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. THE BUILDING |
| | OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY, |
| | OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER |
| | TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM. |
| | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| | RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE |
| | WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. |
| | |
| | 2) THE STRUCTURAL PLANS EXAMINER HAS DETERMINED THE |
| | OCCUPANT LOADS FOR THE MULTI-USE AREAS TO BE GREATER |
| | THAN THE LOADS USED IN THE VENTILATION CALULATION ON |
| | SHEET M1.1. IF THE ENGINEER IS CHOOSING TO USE THE |
| | EXCEPTION UNDER SECTION 403.3, AS HE IS STATING IN THE |
| | RESPONSE NARRATIVE, THEN SUFFICIENT DOCUMENTATION MUST |
| | BE SUBMITTED TO JUSTIFY THE REDUCED OCCUPANT LOAD AND |
| | O/A REQUIERMENT- SEE SECTION 403.3 EXCEPTION. |
| | |
| | 3) REFER TO SECTION 504.5 AND PROVIDE A MEANS OF MAKEUP |
| | AIR FOR THE DRYER IN THE CLOSET. |
| | |