2016-05-05 11:01:25 
  
  
 1. BREAK ROOM SINK SK-2 NEEDS TO RUN THRU GREASE TRAP
  
 2. .ELECTRIC ROOM FLOOR DRAIN NEEDS A TRAP PRIMER
 INASTALLED
  
 3 . TRIPLE SINK NEEDS TO BE VENTED
  
 4. W/M NEED TO SHOW VTR SIZE
  
 5. PLEASE SUBMIT 2 COPIES OF CODE COMPLIANT SANITARY
 RISER DIAGRAMS
  
 6. SHOW VENTING OF FIXTURES ACCORDANCE TO FBC- PLUMBING
 SECTION 901.2.1
  