Plan Review Notes
Plan Review Notes For Permit 16041276
Permit Number 16041276
Review Stop M
Sequence Number 1
Notes
Date Text
2016-05-10 15:17:171ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16041276
 5/10/16
  
 1) M1.1: THE VENTILATION CALCULATIONS DO NOT INCLUDE
 BREAKDOWNS FOR THE CLASSROOMS AND THE ACTIVITY ROOM.
 2) M1.1: THE VENTILATION CALCULATIONS APPEAR TO BE
 INCORRECT FOR THE MULTI-USE ASSEMBLY WHICH MUST BE
 BASED ON AN OCCUPANT DENSITY OF 100 PERSONS PER 1000 SF
 PER TABLE 403.3.
 3) REFER TO SECTION 507.2.2 FBC-14 MECHANICAL AND
 PROVIDE SPECIFACATIONS FOR THE OVEN AND MICROWAVE IN
 THE KITCHENETTE. IF A HEAT HOOD IS NOT TO BE INSTALLED
 PROVIDE AN EXHAUST VENTILATION CALCULATION,
 4) REFER TO SECTION C403.2.5.1 FBC-14 ENERGY
 CONSERVATION: DEMAND CONTROLLED VENTILATION IS REQUIRED
 FOR THE MULTI-USE ASSEMBLY ROOM, ACTIVITY ROOM, AND
 CLASSROOMS. INDICATE A MEANS OF COMPLIANCE ON THE PLANS
 AND PROVIDE SPECIFICATIONS.
 5) PROVIDE A MECHANICAL ROOF PLAN WITH CLEARANCE
 DISTANCE MEASUREMENTS FOR THE O/A INTAKES TO EXHAUST
 OUTLETS AND VENTS, AND THE DISTANCES FROM EQUIPEMENT TO
 ROOF EDGES- SEE SECTIONS 401.4 AND 304.11.
 6) PROVIDE WIND LOAD TIE-DOWN ENGINEERING FOR
 INSTALLATION OF THE RTU'S AND RTU CURBS- SECTION
 301.15.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  