Plan Review Notes
Plan Review Notes For Permit 16041276
Permit Number 16041276
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-05-03 13:03:05THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A 2.20 - THE MAIN ACTIVITY ROOM OCCUPACNY LOAD
 CLACULATION INDICATES 46.1; HOWEVER, 6 TABLES WITH 8
 CHAIRS, 6 SITTING CHAIRS AND 3 BAR CHAIRS ARE SHOWN
 INDICATING 57 SITTING PLACES; EXCEEDING THE OCCUPATION
 LOAD.
  
 PLEASE CORRECT OR CLARIFY.
  
 2) SHEET A 2.20 - DOORS D107 & D 111 INDICATING
 IN-SWINGING AGAINST THE FLOW OF EGRESS.
  
 PER SECTION NFPA 101, DOOR SWING DIRECTION, 7.2.1.4.2,
 DOOR IS REQUIRED TO SWING IN THE DIRECTION OF EGRESS
 TRAVEL FOR AN OCCUPANT LOAD OF 50 OR GREATER PERSONS.
 THECOMBINED OCCUPANCY LOAD EXCEEDS 50.
  
 PLEASE CORRECT.
  
 3) SHEET A 2.20 - THERE ARE STORAGE ROOMS AND A LAUNDRY
 ROOM INDICATED. PER NFPA CAHPTER 16
  
 16.3.2 PROTECTION FROM HAZARDS.
 16.3.2.1 ROOMS OR SPACES FOR THE STORAGE, PROCESSING,
 OR USE OF MATERIALS SPECIFIED IN 16.3.2.1(1) THROUGH
 (3) SHALL BE PROTECTED IN ACCORDANCE WITH THE
 FOLLOWING:
 (1) SEPARATION FROM THE REMAINDER OF THE BUILDING BY
 FIRE BARRIERS HAVING A MINIMUM 1-HOUR FIRE RESISTANCE
 RATING, OR PROTECTION OF SUCH ROOMS BY AUTOMATIC
 EXTINGUISHING SYSTEMS AS SPECIFIED IN SECTION 8.7, IN
 THE FOLLOWING AREAS:
 (A) BOILER AND FURNACE ROOMS, UNLESS SUCH ROOMS ENCLOSE
 ONLY AIR-HANDLING EQUIPMENT
 (B) ROOMS OR SPACES USED FOR THE STORAGE OF COMBUSTIBLE
 SUPPLIES IN QUANTITIES DEEMED HAZARDOUS BY THE
 AUTHORITY HAVING JURISDICTION
 (C) ROOMS OR SPACES USED FOR THE STORAGE OF HAZARDOUS
 MATERIALS OR FLAMMABLE OR COMBUSTIBLE LIQUIDS
 INQUANTITIES DEEMED HAZARDOUS BY RECOGNIZED STANDARDS
 (D) JANITOR CLOSETS
  
 (2) SEPARATION FROM THE REMAINDER OF THE BUILDING BY
 FIRE BARRIERS HAVING A MINIMUM 1-HOUR FIRE RESISTANCE
 RATING AND PROTECTION OF SUCH ROOMS BY AUTOMATIC
 EXTINGUISHING SYSTEMS AS SPECIFIED IN SECTION 8.7 IN
 THE FOLLOWING AREAS:
 (A)* LAUNDRIES
 (B) MAINTENANCE SHOPS, INCLUDING WOODWORKING AND
 PAINTING AREAS
 (C) ROOMS OR SPACES USED FOR PROCESSING OR USE OF
 COMBUSTIBLE SUPPLIES DEEMED HAZARDOUS BY THE AUTHORITY
 HAVING JURISDICTION
 (D) ROOMS OR SPACES USED FOR PROCESSING OR USE OF
 HAZARDOUS MATERIALS OR FLAMMABLE OR COMBUSTIBLE LIQUIDS
 IN QUANTITIES DEEMED HAZARDOUS BY RECOGNIZED STANDARDS.
  
 PLEASE PROVIDE FOR PROPER PROTECTION FROM THESE AREAS.
  
 4) SHEET A 2.00 - NOTE E INDICATES A 30" BUILT-IN OVEN.
 PER NFPA CHAPTER 16
  
 16.3.2.3 COOKING FACILITIES SHALL BE PROTECTED IN
 ACCORDANCE WITH 9.2.3, UNLESS OTHERWISE PERMITTED BY
 16.3.2.4 OR 16.3.2.5.
 16.3.2.4 OPENINGS SHALL NOT BE REQUIRED TO BE PROTECTED
 BETWEEN FOOD PREPARATION AREAS AND DINING AREAS.
 16.3.2.5 APPROVED DOMESTIC COOKING EQUIPMENT USED FOR
 FOOD WARMING OR LIMITED COOKING SHALL NOT BE REQUIRED
 TO BE PROTECTED.
  
 PLEASE PROVIDE DETAILS AND ENFORCEMENT POLICIES TO
 COMPLY WITH THE ABOVE OF 9.2.3 SHALL APPLY.
  
 9.2.3 COMMERCIAL COOKING EQUIPMENT. COMMERCIAL COOKING
 EQUIPMENT SHALL BE IN ACCORDANCE WITH NFPA 96, STANDARD
 FORVENTILATION CONTROL AND FIRE PROTECTION OF
 COMMERCIAL COOKING OPERATIONS, UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE PERMITTED TO BE CONTINUED IN SERVICE.
  
  
 5) SHEET A 2.20 - THERE ARE ROOMS THAT INDICATE MEETING
 SPACE FOR CLEINTS. PER NFPA 101, CHAPOTER 16
  
 16.2.11.1 WINDOWS FOR RESCUE.
 16.2.11.1.1 EVERY ROOM OR SPACE NORMALLY SUBJECT TO
 CLIENT OCCUPANCY, OTHER THAN BATHROOMS, SHALL HAVE NOT
 LESS THAN ONE OUTSIDE WINDOW FOR EMERGENCY RESCUE THAT
 COMPLIES WITH ALL OF THE FOLLOWING, UNLESS OTHERWISE
 PERMITTED BY 16.2.11.1.2:
  
 PLEASE PROVIDE.
  
 ADDITIONAL COMMENTS MAY BE ADDED BASED ON THE
 RESUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  
  
  
  
  