| Date |
Text |
| 2016-05-10 09:12:18 | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. PLEASE CLARIFY THE CONTACTOR SHOWN ON ONE-LINE RISER | | | DIAGRAM FOR PORTABLE GENERATOR SHOWN. PER NEC 702.5, A | | | LISTED TRANSFER SWITCH IS TO USED IN THIS APPLICATION. | | | 2. PROVIDE A NOTE TO PROVIDE TAMPER RESISTANT | | | RECEPTACLES FOR THE CLASSROOM AREA AS SHOWN ON FLOOR | | | PLAN. NEC 406.14 | | | 3. SHOW THAT THERE IS A WP/GFCI RECEPTACLE WITHIN 25FT | | | OF THE ROOFTOP UNITS, SHOW LOADS ON PANEL SCHEDULE. NEC | | | 210.63 | | | 4. PROVIDE A NOTE TO INDICATE REQUIRED LOW VOLTAGE | | | SYSTEMS (ACCESS, DATA ETC.) SEPARATE PERMITS. A NOTE | | | WILL SUFFICE. | | | 5. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | | QUESTIONS REGARDING THIS PROJECT. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|