2016-05-10 09:12:18APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE CLARIFY THE CONTACTOR SHOWN ON ONE-LINE RISER
 DIAGRAM FOR PORTABLE GENERATOR SHOWN. PER NEC 702.5, A
 LISTED TRANSFER SWITCH IS TO USED IN THIS APPLICATION.
 2. PROVIDE A NOTE TO PROVIDE TAMPER RESISTANT
 RECEPTACLES FOR THE CLASSROOM AREA AS SHOWN ON FLOOR
 PLAN. NEC 406.14
 3. SHOW THAT THERE IS A WP/GFCI RECEPTACLE WITHIN 25FT
 OF THE ROOFTOP UNITS, SHOW LOADS ON PANEL SCHEDULE. NEC
 210.63
 4. PROVIDE A NOTE TO INDICATE REQUIRED LOW VOLTAGE
 SYSTEMS (ACCESS, DATA ETC.) SEPARATE PERMITS. A NOTE
 WILL SUFFICE.
 5. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  
  