| 2016-05-05 11:41:59 | 2001 SOUTH DIXIE HIGHWAY |
| | PERMIT #16041215 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW |
| | EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE |
| | BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE |
| | ORDERED FROM WWW.KNOXBOX.COM |
| | |
| | GENERAL: PROVIDE PANIC HARDWARE FOR ALL EGRESS DOORS |
| | SUBJECT TO 50 OR MORE PERSONS. SEVERAL DOORS MISSING |
| | PANIC HARDWARE INCLUDING DOORS 114, 114A, 114B, 119, |
| | 121, 200 AND 204. |
| | |
| | SHEET A050 & SHEET A101: THESE SHEETS ARE IN CONFLICT |
| | WITH EACHOTHER. ONE SHEET INDICATES CLASSROOM AND THE |
| | OTHER SHEET INDICATES MULTI-PURPOSE USE. MULTI-PURPOSE |
| | ROOM #114 IS SHOWN UTILIZING AN OCCUPANT LOAD FACTOR 20 |
| | SQUARE FEET PER PERSON IN LIEU OF 15 SQUARE FEET PER |
| | PERSON. |
| | |
| | SHEET A101: 2ND GRADE CLASSROOM #107 EGRESS DOOR |
| | APPEARS TO OBSTRUCT THE CORRIDOR. PER SECTION 7.2.1.4.3 |
| | DOOR LEAF ENCROACHMENT - DURING ITS SWING, ANY DOOR |
| | LEAF IN A MEANS OF EGRESS SHALL LEAVE NOT LESS THAN |
| | ONE-HALF OF THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR, |
| | A PASSAGEWAY, OR A LANDING UNOBSTRUCTED AND SHALL |
| | PROJECT NOT MORE THAN 7-INCHES INTO THE REQUIRED WIDTH |
| | OF AN AISLE, A CORRIDOR, A PASSAGEWAY, OR A LANDING, |
| | WHEN FULLY OPEN. |
| | |
| | SHEET A101: CORRIDOR EGRESS HAS THE POTENTIAL TO BE |
| | RESTRICTED WITH SECURITY DOOR/GRILL #100A. THIS IS NOT |
| | PERMITTED EVEN WITH FIRE ALARM INTEGRATION. |
| | |
| | SHEET A102: WHAT AGE GROUPS ARE INTENDED TO OCCUPY |
| | CLASSROOMS #202 AND #203. |
| | |
| | SHEET E101: CARD READER SHOWN ON EGRESS SIDE OF MAIN |
| | EXIT DOOR #100. |
| | |
| | SHEET E202: COULD NOT LOCATE EXTERIOR EMERGENCY |
| | LIGHTING FOR STAIR #2. |
| | |
| | GENERAL: IS ANY COMMERCIAL COOKING PROPSED AT THE |
| | SCHOOL? |
| | |
| | FIRE SPRINKLER: ENGINEERED FIRE SPRINKLER CONSTRUCTION |
| | DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT. |
| | AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE |
| | SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS |
| | (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS) |
| | FOR A SUB-PERMIT. PER FLORIDA ADMINISTRATIVE CODE |
| | SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING |
| | DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE |
| | WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS |
| | APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD |
| | OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM |
| | TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP |
| | DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED |
| | INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS. |
| | |