| Plan Review Notes For Permit 16041214 |
| Permit Number |
16041214 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-02 11:17:44 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) THE NATURE OF FIRE ALARM WORK MAY REQUIRE A FIRE | | | WATCH WHEN APPLICABLE' | | | | | | PER NFPA 72, CHAPTER 10, CIRCUITS AND PATHWAYS | | | | | | 10.19* IMPAIRMENTS. | | | | | | 10.19.3* WHERE REQUIRED, MITIGATING MEASURES ACCEPTABLE | | | TO THE AUTHORITY HAVING JURISDICTION SHALL BE | | | IMPLEMENTED FOR THE PERIOD THAT THE SYSTEM IS IMPAIRED. | | | | | | NFPA 101, CHAPTER 9, BUILDING SERVICE AND FIRE | | | PROTECTION EQUIPMENT | | | | | | 9.6.1.6* WHERE A REQUIRED FIRE ALARM SYSTEM IS OUT OF | | | SERVICE FOR MORE THAN 4 HOURS IN A 24-HOUR PERIOD, THE | | | AUTHORITY HAVING JURISDICTION SHALL BE NOTIFIED, AND | | | THE BUILDING SHALL BE EVACUATED, OR AN APPROVED FIRE | | | WATCH SHALL BE PROVIDED FOR ALL PARTIES LEFT | | | UNPROTECTED BY THE SHUTDOWN UNTIL THE FIRE ALARM SYSTEM | | | HAS BEEN RETURNED TO SERVICE. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | |
|