2016-07-21 09:40:26ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 &
 NFPA 70 2011 (NEC)
  
 JOB NAME: 215 5TH STREET
 JOB ADDRESS: 215 5TH STREET
 DESCRIPTION: FACP & COMMUNICATOR REPLACEMENT
 MAST. PERMIT: 16041211
 REVISION/SUB-PERMIT:
  
 1. NFPA 10.5.5.2 CIRCUIT IDENTIFICATION &
 ACCESSIBILITY: THE LOCATION OF THE BRANCH CIRCUIT
 DISCONNECTING MEANS SHALL BE LEGIBLY IDENTIFIED. BE
 PROPERLY MARKED AND SECURED OR BE ACCESSIBLE ONLY TO
 QUALIFIED PERSONS.
 2. FBC-B907.1.2 HAS SPECIFIC REQUIREMENTS FOR THE
 CONTENTS OF THE SUBMITTED SHOP DRAWINGS WHICH HAVE NOT
 BEEN COMPLIED WITH. CORRECT THE DRAWINGS TO INCLUDE THE
 LOCATION OF THE POWER SOURCE, BATTERY CALCULATIONS,
 CONDUCTOR TYPE AND SIZING, VOLTAGE DROP CALCULATIONS,
 MANUFACTURERS SPEC SHEETS FOR ALL APPARATUS AND MOST
 IMPORTANTLY NOTE THE CEILING HEIGHT FOR THE
 RETAIL/DISPLAY AREAS. NOTE THAT W/O THE ACTUAL LAYOUT
 PROPER NOTIFICATION DEVICE PLACEMENT CAN?T BE SECURED.
 THIS WILL BE SUBJECT TO FIELD INSPECTOR?S APPROVAL.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  