| 2016-07-21 09:40:26 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 & |
| | NFPA 70 2011 (NEC) |
| | |
| | JOB NAME: 215 5TH STREET |
| | JOB ADDRESS: 215 5TH STREET |
| | DESCRIPTION: FACP & COMMUNICATOR REPLACEMENT |
| | MAST. PERMIT: 16041211 |
| | REVISION/SUB-PERMIT: |
| | |
| | 1. NFPA 10.5.5.2 CIRCUIT IDENTIFICATION & |
| | ACCESSIBILITY: THE LOCATION OF THE BRANCH CIRCUIT |
| | DISCONNECTING MEANS SHALL BE LEGIBLY IDENTIFIED. BE |
| | PROPERLY MARKED AND SECURED OR BE ACCESSIBLE ONLY TO |
| | QUALIFIED PERSONS. |
| | 2. FBC-B907.1.2 HAS SPECIFIC REQUIREMENTS FOR THE |
| | CONTENTS OF THE SUBMITTED SHOP DRAWINGS WHICH HAVE NOT |
| | BEEN COMPLIED WITH. CORRECT THE DRAWINGS TO INCLUDE THE |
| | LOCATION OF THE POWER SOURCE, BATTERY CALCULATIONS, |
| | CONDUCTOR TYPE AND SIZING, VOLTAGE DROP CALCULATIONS, |
| | MANUFACTURERS SPEC SHEETS FOR ALL APPARATUS AND MOST |
| | IMPORTANTLY NOTE THE CEILING HEIGHT FOR THE |
| | RETAIL/DISPLAY AREAS. NOTE THAT W/O THE ACTUAL LAYOUT |
| | PROPER NOTIFICATION DEVICE PLACEMENT CAN?T BE SECURED. |
| | THIS WILL BE SUBJECT TO FIELD INSPECTOR?S APPROVAL. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |