| Plan Review Notes For Permit 16041211 |
| Permit Number |
16041211 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-06-23 11:17:04 | 215 5TH STREET | | | PERMIT #16041211 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PLANS INDICATE "NTS." SUBMIT SCALABLE PLANS. | | | | | | OFFICE AREAS WILL REQUIRE APPROXIMATELY 55DB SOUND | | | LEVELS IN ALL SPACES PER NFPA 72. PROVIDING | | | NOTIFICATION APPLIANCES IN OPEN SPACES AND CORRIDORS | | | ONLY WILL PROVIDE A CHALLENGE IN OBTAINING ADEQUATE | | | SOUND LEVELS IN ALL ROOMS WITH DOORS. INSPECTOR WILL | | | FIELD VERIFY WITH DB METER. | | | | | | FIRST FLOOR: INADEQUATE HORN-STROBE COVERAGE FOR NORTH | | | FLOOR AREA. | | | | | | SECOND FLOOR: INADEQUATE APPLIANCE COVERAGE IN NORTH | | | WORKROOM. NO APPLIANCE PROVIDED IN BREAKROOM. WHAT IS | | | THE SOUTH UNNAMED ROOM ADJACENT TO THE STORAGE ROOM? | | | | | | THIRD FLOOR: LARGE WORK AREA HAS INADEQUATE COVERAGE IN | | | THE SOUTHWEST CORNER. NO APPLIANCE PROVIDED IN THE | | | CONFERENCE ROOM. | | | | | | PENTHOUSE: NO AUDIBLE COVERAGE PROVIDED FOR ALL | | | PENTHOUSE SPACES. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | | | | |
|