 PERMIT #16041211
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLANS INDICATE "NTS." SUBMIT SCALABLE PLANS.
  
 OFFICE AREAS WILL REQUIRE APPROXIMATELY 55DB SOUND
 LEVELS IN ALL SPACES PER NFPA 72. PROVIDING
 NOTIFICATION APPLIANCES IN OPEN SPACES AND CORRIDORS
 ONLY WILL PROVIDE A CHALLENGE IN OBTAINING ADEQUATE
 SOUND LEVELS IN ALL ROOMS WITH DOORS. INSPECTOR WILL
 FIELD VERIFY WITH DB METER.
  
 FIRST FLOOR: INADEQUATE HORN-STROBE COVERAGE FOR NORTH
 FLOOR AREA.
  
 SECOND FLOOR: INADEQUATE APPLIANCE COVERAGE IN NORTH
 WORKROOM. NO APPLIANCE PROVIDED IN BREAKROOM. WHAT IS
 THE SOUTH UNNAMED ROOM ADJACENT TO THE STORAGE ROOM?
  
 THIRD FLOOR: LARGE WORK AREA HAS INADEQUATE COVERAGE IN
 THE SOUTHWEST CORNER. NO APPLIANCE PROVIDED IN THE
 CONFERENCE ROOM.
  
 PENTHOUSE: NO AUDIBLE COVERAGE PROVIDED FOR ALL
 PENTHOUSE SPACES.
  