| Plan Review Notes For Permit 16041189 |
| Permit Number |
16041189 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-07-01 17:13:39 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT 16041189 | | | 7/1/2016 | | | | | | 1) THE SUBMITTED ENERGY FORM C402 2014 MUST BE SIGNED | | | BY THE OWNER. | | | | | | 2) PLEASE INDICATE THE MAKE AND MODEL OF THE EXISTING | | | RTU ON THE PLAN AND ITS COOLING AND HEATING CAPACITY. | | | PLEASE NOTE THAT A DUCT SMOKE DETECTOR WILL REQUIRED | | | FOR A 5-TON SYSTEM THAT CAN PRODUCE OVER 2000 CFMS PER | | | MANUFACTURER'S SPECIFICATIONS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|