2016-04-29 15:56:511ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16041189
 4/29/16
  
 1) SHEET M201, ROOF CURB ADAPTER DETAIL: A) PROVIDE THE
 WIND LOAD DESIGN CRITERIA- SECTION 301.15 MECHANICAL.
 B) PROVIDE COMPLETE FASTENING DETAILS FOR ATTACHING THE
 CURB ADAPTER TO THE EXISTING CURB, THE CURB TO THE ROOF
 STRUCTURE, AND THE RTU TO THE CURB ADAPTER. C) SUBMIT
 MANUFACTURER'S PRODUCT DATA SHEETS FOR THE CURB ADAPTOR
 WITH A APPROVAL SIGNATURE BY THE ENGINEER OF RECORD.
 2) SUBMIT MANUFACTURER'S PRODUCT DATA SHEETS FOR THE
 NEW 5-TON TRANE MODEL TCH060E4.
  