| 2016-04-29 15:56:51 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16041189 | | | 4/29/16 | | | | | | 1) SHEET M201, ROOF CURB ADAPTER DETAIL: A) PROVIDE THE | | | WIND LOAD DESIGN CRITERIA- SECTION 301.15 MECHANICAL. | | | B) PROVIDE COMPLETE FASTENING DETAILS FOR ATTACHING THE | | | CURB ADAPTER TO THE EXISTING CURB, THE CURB TO THE ROOF | | | STRUCTURE, AND THE RTU TO THE CURB ADAPTER. C) SUBMIT | | | MANUFACTURER'S PRODUCT DATA SHEETS FOR THE CURB ADAPTOR | | | WITH A APPROVAL SIGNATURE BY THE ENGINEER OF RECORD. | | | 2) SUBMIT MANUFACTURER'S PRODUCT DATA SHEETS FOR THE | | | NEW 5-TON TRANE MODEL TCH060E4. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|