Plan Review Notes
Plan Review Notes For Permit 16041182
Permit Number 16041182
Review Stop E
Sequence Number 1
Notes
Date Text
2016-04-27 15:57:17REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 - PROVIDE LOAD CALCULATIONS AND A PANEL SCHEDULE
 REFLECTING EXISTING CIRCUITS. NEC 215.5 , WPBA 107.
  
 - NEC 250.94 PROVIDE AN INTERSYSTEM BONDING STRIP
 TERMINAL.
  
 - NEC 230.70 LOCATE THE SERVICE DISCONNECT IN THE
 NEAREST POINT OF ENTRANCE. CLARIFY DISTANCE FROM THE
 OUTSIDE TO THE INSIDE OF THE BUILDING ?