| Plan Review Notes For Permit 16041182 |
| Permit Number |
16041182 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-04-27 15:57:17 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | [email protected] | | | | | | | | | - PROVIDE LOAD CALCULATIONS AND A PANEL SCHEDULE | | | REFLECTING EXISTING CIRCUITS. NEC 215.5 , WPBA 107. | | | | | | - NEC 250.94 PROVIDE AN INTERSYSTEM BONDING STRIP | | | TERMINAL. | | | | | | - NEC 230.70 LOCATE THE SERVICE DISCONNECT IN THE | | | NEAREST POINT OF ENTRANCE. CLARIFY DISTANCE FROM THE | | | OUTSIDE TO THE INSIDE OF THE BUILDING ? |
|