| Plan Review Notes For Permit 16041163 |
| Permit Number |
16041163 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-04-28 17:54:59 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | [email protected] | | | | | | -NEC 2108 B GFCI PROTECTION REQUIRED FOR GARAGE DOOR | | | MOTOR RECEPTACLE OUTLET. | | | -FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE | | | SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE | | | LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON | | | FLOOR PLAN. REFLECT NEW LOADS OF DRYER , WASHER , AND | | | A/C MINI SPLIT. | | | -NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125 VOLT, | | | SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE OUTLET | | | SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE | | | SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL BE | | | LOCATED WITHIN 25 FT. OF THE EQUIPMENT. | | | |
|