Plan Review Notes
Plan Review Notes For Permit 16041163
Permit Number 16041163
Review Stop E
Sequence Number 1
Notes
Date Text
2016-04-28 17:54:59REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
 -NEC 2108 B GFCI PROTECTION REQUIRED FOR GARAGE DOOR
 MOTOR RECEPTACLE OUTLET.
 -FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN. REFLECT NEW LOADS OF DRYER , WASHER , AND
 A/C MINI SPLIT.
 -NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125 VOLT,
 SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE OUTLET
 SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE
 SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED WITHIN 25 FT. OF THE EQUIPMENT.
  