| Plan Review Notes For Permit 16041150 |
| Permit Number |
16041150 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-20 08:56:06 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | - PROVIDE SPECS ON POOL EQUIPMENT POOL HEATERS AND POOL | | | PUMPS. FBC 107 INSUFFICIENT DOCUMENTS. | | | | | | - SPECIFY WHETHER LIGHT NICHE REQUIRES # 8 AWG BONDING | | | CONDUCTOR OR NOT ? NEC 680.22(B)(2)/680.24, IF NOT HOW | | | WILL POOL WATER BE BONDED ? NEC 680.26(C) | | | | | | - GENERAL COMMENT GFC PROTECTION REQUIRED FOR POOL | | | PUMPS , LIGHTS , RECEPTACLES. NEC 680.21, 680.22. | | | | | | |
|