| 2016-06-08 14:42:48 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16041150 |
| | ADD: 333 FERN ST/ POOL 7TH FLOOR LEVEL |
| | CONT: A & G CONCRETE POOLS |
| | TEL: 772-878-7752 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JUNE 08/2016 |
| | ACTION: DENIED |
| | |
| | NOTE: THIS REVIEW IT IS UNDERSTOOD THE PRIME BUILDING |
| | PERMIT: 15031312 IS FOR A R-2 APARTMENT COMPLEX/ FAIR |
| | HOUSING DOES NOT REQUIRE AN ACCESSIBLE ENTRANCE INTO |
| | THE SWIMMING POOL. |
| | |
| | 1) THE SHEET 4 POOL EQUIPMENT ROOM LAYOUT SHOWS A |
| | HEATER BUT THERE ARE NO MANUFACTURERS SPEC ON THE |
| | HEATER. RESPONSE COMMENTS FROM ACE AQUATIC CONSULTING |
| | COMMENT # 11 INDICATES THERE ARE MANUFACTURERS SPEC |
| | SHEET ATTACHED TO THIS LETTER. NOT FOUND. THERE ARE |
| | MANUFACTURER'S SPEC ON THE MAIN DRAIN GRATES. 107.2.1.3 |
| | ADDITIONAL INFORMATION REQUIRED. SHOW COMPLIANCE WITH |
| | 2014 FBC-ENERGY CODE |
| | |
| | 2) SHEET 4 SHOWING A HEATER WILL NEED TO SHOW |
| | COMPLIANCE WITH: 2014 FBC-ENERGY CODE C404.7.1 POOL |
| | HEATERS. |
| | ALL POOL HEATERS SHALL MEET THE MINIMUM EFFICIENCY |
| | LISTED FOR THAT TYPE OF POOL HEATER IN TABLE C404.2 AND |
| | BE EQUIPPED WITH A READILY ACCESSIBLE ON-OFF SWITCH |
| | THAT IS MOUNTED OUTSIDE OF THE HEATER TO ALLOW SHUTTING |
| | OFF THE HEATER WITHOUT ADJUSTING THE THERMOSTAT |
| | SETTING. GAS-FIRED HEATERS SHALL NOT BE EQUIPPED WITH |
| | CONSTANT BURNING PILOT LIGHTS. |
| | |
| | 3) WITH THE SWIMMING POOL HAVING A HEATER PLEASE SHOW |
| | COMPLIANCE WITH ENERGY CODE SECTION C404.7.3 COVERS. |
| | HEATED SWIMMING POOLS AND INGROUND PERMANENTLY |
| | INSTALLED SPAS SHALL BE EQUIPPED WITH A VAPOR-RETARDANT |
| | COVER ON OR AT THE WATER SURFACE OR A LIQUID COVER OR |
| | OTHER MEANS PROVEN TO REDUCE HEAT LOSS. |
| | |
| | JAMES A. WITMER CBO |