| 2017-01-24 15:36:48 | 6TH REVIEW FBC-2014 MECHANICAL | | | PERMIT #16041147 | | | 1/24/17 | | | | | | 1) THE ELECTRICAL PLANS AND THE REVISED AC AND ENERGY | | | CALCULATIONS DO NOT MATCH. THE PLANS INDICATE 5 WALL | | | SYSTEMS LOCATED IN THE LIVING ROOMS OF UNITS 1-5. THE | | | REVISED CALCULATIONS ARE FOR 15 WALL SYSTEMS TO BE | | | LOCATED APPARENTLY IN THE LIVING ROOMS AND BEDROOMS OF | | | THE UNITS. PLEASE NOTE THAT THE PANEL SCHEDULES ARE | | | INDICATING ONLY FIVE WALL SYSTEMS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|